TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page
28
of
43
6) Set ActPress Swt2:
By selecting this menu
Set ActPress Swt2
switch type is selected which is going to
connect with cylinder. By default it is
NO type
you can select
NC type
to change the state press
Enter
menu and the use
left
or
right
key. Press
ENTER
key to save the changes.
LCD Display is Shows as below.
6) Set Remote I/P:
By selecting this menu
Set Remote I/P
you can configure Remote I/P as
RM Fire
or
Silence
. By default it is
Remote Fire
you can select
Silence.
To change the state press
Enter
menu and
the use
left
or
right
key. Press
ENTER
key to save the changes.
LCD Display is Shows as below.
3.2.3 Output Config:
From selecting this menu you can Enter below sub menus
1) RAC Config:
After entering in the
RAC Config
menu, LCD displays current setting of RAC Configuration.
In this menu, there are four options available for RAC configuration. Use
left
and
right
keys to move to next
option. To set the particular option, press
ENTER
key.
1.
Z1 & Z2 Cross:
This is the cross zoning option for RAC with only zone 1 and 2. When both zones are in
fire alarm condition then RAC will be released.
2.
Z1 or Z2:
This is the simple zoning option for RAC with any of the two zones. When any of the two zones
is in fire alarm condition then RAC will be released.
3.
Z1 Only:
This is the simple option for RAC release. When only
zone 1
is in fire alarm condition then RAC
will be released.
4.
Z2 Only:
This is the simple option for RAC release. When only
zone 2
is in fire alarm condition then RAC
will be released.
2) Cylinder Type:
After entering in the
Cylinder Type
menu, LCD displays current setting of Cylinder Type
Set ActPres Swt1
NO Type
Set ActPres Swt2
NO Type
Set Remote I/P
Remote Fire
RAC Config
Z1 & Z2 Cross
Cylinder Type
Main