TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page
9
of
43
•
More than 200 records history events for fire alarm, fault condition, RAC release or abort
condition, sequence of events.
1.3 Technical Specifications
Power Supply
180
–
265V AC, 3A, 60/50 Hz.
Input
Initiating Device Circuit (IDC)
•
Voltage:24 VDC
•
End of Line:4.7K
Ω,
1 W
•
Digital Inputs: 3 inputs
Indication
Front panel LED indications
•
SYSTEM ON
•
MAINS FAIL
•
BATTERY FAULT
•
NAC FAULT
•
RAC FAULT
•
COMMUNICATION FAIL
•
SILENCE
•
REMOTE FIRE
•
PRE RELEASE
•
REMOTE RELEASE
•
RAC ABORT
•
RAC RELEASE
•
Wi-Fi
•
FIRE
•
FAULT
•
AUTO
•
MANUAL
•
MAINTENANCE
LED Indications for 2 zones
FIRE, SHORT FAULT, OPEN FAULT, DISABLE
16 x 2 LCD Dot Matrix Display Indication
Zone fire status, fault status, configuration menus, real time
clock