TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page
10
of
43
Buzzer Indication
Fire, Fault, Key press acknowledge
Output
Releasing Appliance Circuit (RAC1, RAC2)
Voltage: 24 VDC, Current: 500mA each.
Notification Appliance Circuit (NAC1, NAC2, NAC3)
Voltage: 24 VDC, Current: 250mA each.
PFC Relay outputs: 3
Dimensions
(365 x 90 x 327) mm (L x W x H)
Operating
Temperature
0
℃
~+50
℃
Humidity
5 to 95% Rh
Enclosure
Mild Steel (thickness 1.2mm) with powder coating,
Colour:RAL7035
1.4 Controls and Indications
1.4.1 Controls
Key name
Key function
MENU
•
Shows all system menus.
•
Configures system as per requirements.
•
Can view history events.
•
Goes back to previous screen.
•
Exits from the menu i.e. ESC.
ENTER
•
Access the new menu.
•
Saves configured data, mode or value of the system.
SILENCE
•
Silence the NACs.
ACK
•
Acknowledge the system.
•
Put OFF local buzzer.
RESET
•
Reset all the system
•
Moves cursor of LCD right with the use of key.
•
Moves cursor of LCD left with the use of key.
•
Moves cursor up with the use of keys.
•
Use to increment Count From 0 to 9
•
Moves cursor down with the use of keys.
•
Use to decrement Count From 9 to 0