NACs retain their status.
•
You can abort RAC within Pre release time.
4.2.4 RAC Released Condition
This is the last status condition in system during fire alarm. The status is visibly indicated on LED and LCD. This
condition occurs after Pre Release time is over. LCD displays as shown below.
For example, RAC1: Auto Release
The System operation for the RAC released condition is given below.
•
Respective RAC Released LED turns ON.
•
Respective Pre Release LED turns OFF provided other pre release time is not running
•
Respective Abort LED turns OFF.
•
Default RAC Released output of the relay (Prg.2 Relay ) gets activated. Pre release output of the relay is
active till system reset.
•
Other relays retain the output status.
•
Other LED retains their status.
•
System latch respective RAC released status till reset.
•
If main cylinder is selected then Main RAC Released or Standby RAC Released message shows on LCD.
•
All events are stored in memory.
•
If it is not auto released, then Manual Pre release timer starts and respective remote Release or manual
release LED turns ON.
•
Internal buzzer retains its status.
•
NAC retains its status.
4.2.5 RAC Abort Condition
This condition occurs when any RAC gets aborted. The status is visibly indicated on LED and LCD. The
respective pre release timer stops and RAC Abort Timer Starts after Abort Timer finished release action gets
cancelled. LCD displays as shown below.
For example, RAC Abort , GAS Inhibit.
The System operation for the RAC Abort condition is given below.
Z1:Alrm Z2:Alrm
11/03/20 17:57
Z1:Alrm Z2:Alrm
11/03/20 17:57