TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page
37
of
43
•
By Pressing RAC Abort RAC abort timer is activated. Screen shows RAC Abort Time : 005 Sec
•
Respective RAC Abort LED turns ON.
•
Respective Pre Release LED turns OFF.
•
Other LED retains their status.
•
System latch respective Abort LED status till next action or system reset.
•
Abort message is shown on LCD.
•
All events are stored in memory.
•
Internal buzzer retains their status.
•
NAC retains their status.
Note: You can abort RAC Release only when Pre realised timer is on.
4.2.6 System Silence
There is one digital input provided to silence the system. Whenever the NAC is ON by means of fire or Drill
operation or any other means, it can be turned OFF using this digital input. LCD displays as shown below.
For example, NAC ON, System Silence Operation
The System operation for the System Silence condition is given below.
•
Silence LED turns ON.
•
NAC output turns OFF.
•
All events are stored in memory.
•
Other LED retains their status.
4.2.7 System Reset
There is one digital input provided to reset the system. To come out from fire latch condition or any other
condition, system is reset. It takes 3-4 sec to complete reset action. LCD displays as shown below.
For example, after system reset, all zones are displayed as per their status.
The System operation for the System Reset condition is given below.
•
All LEDs are reset.
•
NAC output and RAC output also turns OFF.
•
Resetting message displays on LCD.
•
All events are stored in memory.
Z1:Nrml Z2:Nrml
11/03/20 17:57
System Resetting