Vigilant MICROVAC Owner's Manual
Document: LT0109
Installation, Wiring, Setup, and Commissioning
Page 2-10
5 April 2000
Issue 1.31
2.2.16 NETWORK WIRING
On a networked Microvac an ECM board and a SPIF board will be fitted. These should be
wired to the rest of the QE90 system, and their links setup, as described in LT0088 "QE90
Installation and Commissioning Manual" Chapter 20. This manual will have been supplied
with the QE90 ECP(s) supplied with the networked system. The ECM will also need
programming as described in the same chapter of this manual.
2.2.17 MASTER WIP WIRING
On a networked Microvac, a "Master" WIP may optionally be fitted. This is wired to the
solder terminals on a RING9006 PCB which plugs into the RING9006 position of the ECM.
No end of line resistor should be fitted.
2.2.18 FIELD WIP WIRING
On a networked Microvac, an 8 circuit WIP board may optionally be fitted. Up to 8 field WIPs
may be wired to the terminals la1–, +2–, +3–, +4–, +5–, +6–, +7–, +8–. Each field
WIP requires a 10k end of line resistor wired in parallel with the WIP.
Summary of Contents for MICROVAC
Page 34: ......