Page 9-9
AS 4428 System Fault
The remote system has an AS 4428 System Fault,
which may include non-Zone, non-point fault
statuses such as RZDU faults, power supply
faults, network problems, etc.
AS 7240 System Fault
The remote system has an AS 7240 System Fault
condition. See Status Indication page 1-7.
Bell Isolated
The remote system is signalling that its AS 1603
Bell (or equivalent) is disabled.
Bell On
The remote system is signalling that its AS 1603
Bell (or equivalent) is activated.
Brigade Disabled
The remote system is indicating that some or all of
its brigade/monitoring service signalling outputs
are disabled.
Brigade Test
The remote system has its AS 4050(int) Brigade
Test function active.
Common Point Disable
The remote system has one or more points that
are disabled.
Common PreAlarm
The remote system is signalling that one or more
of its detectors are in the Prealarm condition.
Disables Routing Disabled The remote system has its Disables Routing
(monitoring service) disabled.
Disables Routing Fault
The remote system has a fault asociated with its
its Disables Routing system (monitoring service).
Enabled alarms to recall
The remote system is indicating it has one or
more enabled alarm conditions that can be
recalled.
Enabled faults to recall
The remote system is indicating it has one or
more enabled fault condition that can be recalled.
External Strobe Alarm
The remote system has alarm conditions that
would activate the External Strobe.
External Strobe Isolate
The remote system has its External Strobe
disabled/isolated.
External Strobe On
The remote system has its External Strobe
outputs operated.
External Strobe Silence
The remote system is signalling that other panels
can turn off their External Strobe.
Fault Buzzer On
The remote system has its Fault buzzer on.
Fault Routing Disabled
The remote system has its Fault Routing
(monitoring service) disabled.
Fault Routing Fault
The remote system has a fault asociated with its
its Fault Routing system (monitoring service).
FBP AIF Attended
The remote system has its Alarm Investigation
Facility function enabled, and a suitably trained
operator is in attendance.
Group Alarm Devices
Activated
The remote system has local alarm conditions that
are will activate the Alarm Devices.
MAF Alarm
The remote system has a brigade alarm that will
activate the warning system or external strobe.
MAF Alarm No Bells
The remote system has a brigade alarm.
MAF Disable
The remote system has a disable condition that is
signalled to the monitoring service.
MAF Disabled Alarm
The remote system has a disabled brigade alarm.
MAF Disabled Fault
The remote system has a disabled fault.
MAF Fault
Remote system has a fault that is signaled to the
monitoring service.