Vigilant
MX1-Au
Operator Manual
Document: LT0439
Page
23 October 2018
Issue 1.73
11-12
LM0459 and fuse provided with the T-Gen2.
The T-Gen2 can be connected to the ANC1 relay output as shown in
Figure 11-9a. The LM0319 included for this purpose plugs in to the 6 way
header on ANC1. If present, remove the red +VBF and black 0V power
wires from the LM0319.
This wiring provides complete supervision of wiring open and short
circuits, as well as passing the state of the T-G
en2’s fault relay to the
MX1
controller.
ANC2 could be used to control the T-Gen2 instead of ANC1, but this will
require manual wiring as the supplied loom supports only ANC1, and
ANC2 supervision must be set to “Contact”.
When the T-Gen2 Alert tone must be controlled by the
MX1
, one of the
GP OUT terminals can be connected to the T-Gen2
’s A/I/E- input, as
shown in the diagram. This is not default operation, and the
MX1
must
be specially configured.
Figure 11-9a – Wiring Ancillary Relay 1 to T-Gen2 – Grade 3