Vigilant
MX1-Au
Operator Manual
Document: LT0439
Page
23 October 2018
Issue 1.73
6-4
latching devices.
HISTORY
F2
s
ets the point’s History High and History Low values to
the current value, if it has history values. If it does not, this has no
effect. Generally, only analogue addressable detectors have history
values.
TRACK
F3
resets the point’s Tracked value to the current value, if it
has one. If it does not, this has no effect. Generally, only analogue
addressable detectors have Tracked values. This option is useful for
resetting the tracking after a new or cleaned detector has been
installed.
After selecting the type of reset required you will be asked to confirm or
cancel the reset. Pressing
OK
will confirm the reset and display the
recall display for the point concerned. Pressing
CANCEL
will return to
the display shown above.
A range of points can be reset from a base display by using the
RESET
key. Reset options are as shown below.
Do not press the f.b.p.
RESET
key when the Alarm List is
being shown unless the intent is to reset all alarms.
Select an item to reset | ZONE
| POINT
|
|
Fig 6-7 – Selecting An Item To Be Reset
Press
POINT
F2
.
Reset point | -TO-
: |
Enter E.D.S for single point |
or E.D.S F1 E.D.S for range | <-
Fig 6-8 – Enter A Point Range To Be Reset
Enter the first point in the range that is to be reset. Then press
F1
and
enter the last point in the range.
Resetting a
Range of
Points