Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 8-11
Press the
INITIATE
F4 option and MENU twice so that a
SYSTEM
F1 option is shown. Press F1 to show the following screen.
MX1 Vv.vv
Firmware CRC: xxxxxxxx
Config 1 CRC: xxxxxxxx yyyy
Config 2 CRC: xxxxxxxx yyyy
Fig 8-12 – Tests System Screen Shows Firmware and Config CRCs
The top line shows the
MX1
Controller firmware version, Vv.vv. The
second line shows the firmware CRC. The third and fourth lines show
the internal checksum (xxxxxxxx) and CRC (yyyy) for the two
configuration datafiles. The CRC of the datafiles is the CRC as shown by
the SmartConfig Show CRC command and can be used to confirm the
datafiles are identical or the same as the file on the PC.
The Test Alarm Devices command allows all the alarm devices to be
operated simultaneously, for example, during a trial evacuation of the
building. The alarm devices operate until the test is stopped.
From the base display press TESTS,
INITIATE
F4 and press
ALARM
DEV
F3 so the alarm devices test status screen is shown.
Alarm Devices Test: | START
Inactive |
|
|
Fig 8-13 – Alarm Devices Test Status Screen
This shows the status of the test (Inactive or Active) and allows the test
to be started (if the test is inactive) and stopped (if the test is active).
Press
START
F1 to initiate the test
– all alarm devices will operate
unless they have been disabled. Conduct the test and then press
STOP
F4 when complete.
The test can also be started by OpOn testing point 241.1.0 (the Alarm
Devices point) and stopped by resetting this point.
Test Alarm Devices