VIKING TECHNICAL SUPPORT 1.800.908.0884
3 7
TROUBLESHOOTING
# LED
Status
Meaning
Page 41
TS Ref#(s)
9
“C Loop”
OFF
Normal Condition.
SOLID
An input from a device connected to the C Loop terminal. (pg 28, 32)
9, 10
10 “Open”
OFF
Normal Condition.
SOLID
An input from a device to Exit, Fire, Strike or Open terminal. (pg 28, 32)
9, 10
11
“STOP”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the
Stop, UL or Re-Open terminals (pg 28, 32)
9, 10
FLASHING
There is a problem with the required monitored sensor(s) connected to
the “UL” and/or “Re-Open” input terminals (pg 6-7, 22)
16, 20
12 “Close”
OFF
Normal Condition.
SOLID
An input from a device connected to the Close terminal. (pg 28)
9, 10
13 “Siren”
OFF
Normal Condition.
SOLID
Second consecutive obstruction has been detected. (pg 24, 26)
11, 13, 1, 2
FLASHING
Batteries are critically low.
1, 2
14 “Aux. Pwr”
OFF
No voltage output on these terminals at the moment.
SOLID
There is 24V DC output on these terminals at the moment.
15 “Diagnose” (Primary)
OFF
Normal Condition
FLASHING
Errors have been detected; Check LCD Display for ERR messages. (pg 40)
16
“Close Limit” (Primary)
OFF
Gate is not at the close limit position.
SOLID
Gate is at the close limit position.
FLASHING
Indicates a problem with the limit switches or wires.
16,21, 22
17
“Open Limit” (Primary)
OFF
Gate is not at the open limit position.
SOLID
Gate is at the open limit position.
FLASHING
Indicates a problem with the limit switches or wires.
16,21, 22
18 “ODS”
OFF
Normal Condition.
SOLID
Obstruction event has been detected on the Primary motor. (pg 24, 26)
11, 13, 1, 2
FLASHING
Overload event has been detected on the Primary motor. (pg 24, 26)
11, 13, 1, 2
19 “Timer”
OFF
If gate is at the open limit, the Timer to close is turned OFF. (pg 24)
SOLID
Timer to close is ON and counting down to close the gate. (pg 24)
FLASHING
Timer is ON but is not timing out due to a conflicting command. (pg 24)
9, 10
S1 “Diagnose” (Secondary) OFF
Normal Condition
FLASHING
Errors have been detected; Check LCD Display for ERR messages. (pg 40)
SOLID
Obstruction event has been detected on the Secondary motor. (pg 24, 26)
11, 13, 1, 2
RAPID FLSH Overload event has been detected on the Secondary motor. (pg 24, 26)
11, 13, 1, 2
S2
“Limit Close”
(Secondary)
OFF
Secondary gate is not at the close limit position.
SOLID
Secondary gate is at the close limit position.
S3
“Limit Open”
(Secondary)
OFF
Secondary gate is not at the open limit position.
SOLID
Secondary gate is at the open limit position.
E1
“AC VOLTAGE INPUT”
SOLID
Normal Condition.
OFF
Incoming power to the EMI Board is not sufficient..(pg 18)
1
E2
“PROTECTION WORKING”
SOLID
Normal Condition.
OFF
EMI Board is damaged and circuit is not protected . Replace EMI Board.
E3
“AC VOLTAGE OUTPUT”
SOLID
Normal Condition.
OFF
There is no output voltage from the EMI Board.
2