SIDEWALL SPRINKLER 

VK104 (K5.6)

TECHNICAL DATA

Page 5 of 6

Form No. F_033514     19.11.18   Rev 19.4

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

DESIGN CRITERIA - FM 

(Also refer to Approval Chart 2 above.)

FM Approval Requirements:

 

The Micromatic

®

 Viking Standard Response Horizontal Sidewall Sprinkler VK104 is FM Approved as standard response sidewall 

Non-Storage

 sprin-

klers, as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention 

Data Sheets (including 2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guide-

lines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum al-

lowable spacing, and deflector distance below the ceiling.

NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin Form No. 

F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with 

the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar 

organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Approval Chart 1 (FM)

Micromatic

®

 Viking Standard Response Horizontal Sidewall Sprinkler VK104

Maximum 175 PSI (12 Bar) WWP

Sprinkler 

Base Part 

Number

1

SIN

Thread Size

Nominal K-factor

Overall Length

FM Approvals

(Refer also to UL Design Criteria.)

NPT

BSPT

U.S.

metric

2

Inches

mm

12995

VK104

1/2”

--

5.6

80.6

2-1/2”

64

A1Y, B1X, C2Y, D2W

12988

VK104

--

15 mm

5.6

80.6

2-1/2”

64

A1Y, B1X, C2Y, D2W

20230

6

VK104

--

15 mm

5.6

80.6

2-1/2”

64

E3

NOTICE - Product Below - No longer offered.

10224

VK104

1/2”

--

5.6

80.6

2-1/2”

64

A1Y, B1X

10171

VK104

--

15 mm

5.6

80.6

2-1/2”

64

A1Y, B1X

Approved Temperature Rating Codes

A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)

B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)

C = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)

D = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C)

E = 155 °F (68 °C)

Approved Finish Code

Approved Escutcheon Codes

1 = Brass and Chrome

2 = ENT

5

3 = Chrome

X = Standard surface-mounted escutcheons or recessed with the Viking Model E-1, E-2, E-3, or G-1 Recessed Escutcheons

Y = Standard surface-mounted escutcheons only

W = Standard surface-mounted escutcheons or recessed with the Viking Model E-1 Recessed Escutcheons

Footnotes

1. 

Base part number shown. For complete part number, refer to Viking’s current price schedule.

2. 

Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3. 

This table shows the listings and approvals available at the time of printing. Other approvals may be in process.

4. 

Listings and Approvals are limited to Light Hazard Occupancies where allowed by the installation standards being applied.

5. 

FM Approved as corrosion resistant.

6. 

Approved according to China GB standard.

Summary of Contents for 10171

Page 1: ... 500 psi 34 5 bar Nominal K Factor 5 6 U S 80 6 metric Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1 2 64 mm Material Standards Frame Casting Brass UNS C84400 or QM Brass Deflector Copper UNS C19500 Bulb Glass nominal 5 mm diameter Bel...

Page 2: ...h the following temperature ratings 155 F 68 C Lt Brown Wax 175 F 79 C Brown Wax 200 F 93 C Brown Wax 286 F 141 C Dk Brown Wax5 Accessories Sprinkler Wrenches see Figure 1 A Standard Wrench Part No 21475M B B Standard Wrench for Wax Coated Sprinklers Part No 10896W B C Socket Wrench for Recessed Pendent Sprinklers Part No 13655W B A 1 2 ratchet is required not available from Viking D Socket Wrench...

Page 3: ...iking website for the latest edition of this technical data page www vikinggroupinc com Figure 3 Recessed Sprinkler Installation A 1 2 ratchet is required which is not available from Viking Step 1 Carefully slide the wrench sideways around the deflector ensuring engagement with the sprinkler wrench flats Step 2 Carefully press the wrench onto the sprinkler wrench flats Figure 1 Sprinkler Wrenches ...

Page 4: ...l K factor Overall Length Listings and Approvals3 Refer also to UL Design Criteria NPT BSPT U S metric2 Inches mm cULus4 LPCB MED CE8 China Approval 12995 VK104 1 2 5 6 80 6 2 1 2 64 A1Z B1X B2X C4Z E4Y A1Z B2Z C19 C1Z8 12988 VK104 15 mm 5 6 80 6 2 1 2 64 A1Z B1X B2X C4Z E4Y A1Z B2Z C19 C1Z8 2023010 VK104 15 mm 5 6 80 6 2 1 2 64 D3 D3 NOTICE Product Below No longer offered 10224 VK104 1 2 5 6 80 6...

Page 5: ...so with the provisions of governmental codes ordinances and standards whenever applicable Approval Chart 1 FM Micromatic Viking Standard Response Horizontal Sidewall Sprinkler VK104 Maximum 175 PSI 12 Bar WWP Sprinkler Base Part Number1 SIN Thread Size Nominal K factor Overall Length FM Approvals3 Refer also to UL Design Criteria NPT BSPT U S metric2 Inches mm 12995 VK104 1 2 5 6 80 6 2 1 2 64 A1Y...

Page 6: ...e latest edition of this technical data page www vikinggroupinc com Surface Mounted Escutcheon 2 1 4 58 mm 2 1 16 52 mm 2 1 4 57 mm 2 1 4 57 mm 1 7 16 37 mm 1 7 16 37 mm 1 7 16 37 mm Maximum Maximum Maximum Minimum Minimum Minimum Model E 1 Recessed Escutcheon Wall Opening Size Maximum 2 1 2 64 mm Minimum 2 5 16 57 mm Model E 3 Recessed Escutcheon Model E 2 Recessed Escutcheon Figure 4 Installatio...

Page 7: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 8: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 9: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 10: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 11: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: