background image

ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 2 of 6

Form No. F_120106    19.11.15    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Compression Screw: Stainless Steel UNS-S31603

Trigger and Support: Stainless Steel UNS-S31600

Fusible Element Assembly: Beryllium Nickel, coated with black acrylic paint.

Ordering Information:

 (Also refer to the current Viking price list.)

Order ESFR Pendent K16.8 Sprinkler VK503 by first adding the appropriate suffix for the sprinkler finish and then the appropriate 

suffix for the temperature rating to sprinkler base part number.

Finish Suffix: Brass = A

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E

For example, sprinkler VK503 with a Brass finish and a 165 °F (74 °C) temperature rating = Part No. 14073AC. 

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench: 

Part No. 13635WB (double-ended wrench - Use Side A. Side B is for use with K25.2 ESFR Pendent Sprinkler 

VK510) Available since 2006.

Sprinkler Cabinet: 

Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

A. Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install 

sprinklers that have been dropped or damaged in any way. Such sprinklers should be destroyed immediately. 

NOTE: Wet pipe systems must be provided with adequate heat.

B. The sprinklers must be installed after the piping is in place to prevent mechanical damage. Before installing, be sure to have the 

appropriate sprinkler model and style, with the correct orifice size, temperature rating, and response characteristics.

C. With the sprinkler contained in the plastic protective cap, apply a small amount of pipe-joint compound or tape to the male threads 

only, while taking care not to allow a build-up of compound in the sprinkler orifice.

D. 

Use ONLY sprinkler wrench 13635WB (shown in Figure 1) for installing ESFR Sprinkler VK503! With the sprinkler con-

tained in the protective cap, install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench 

flats only, while taking care not to damage the sprinkler operating parts.

DO NOT use any other type of wrench, as this could damage the unit.

DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting.

DO NOT exceed 50 ft. lbs. of torque (hand tight, plus approximately two full turns with the wrench) to install these sprinklers. Higher 

levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

E. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the Installation Standards. 

Make sure the sprinkler has been properly tightened. If a thread leak occurs, normally the unit must be removed, new pipe-joint 

compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing compound 

or tape is washed out of the joint. Immediately replace any damaged units, using the special sprinkler wrench only.

F. After installation and testing and repairing of all leaks, remove the protective caps from the sprinklers. Do NOT use any 

type of tool to remove the cap. Remove the cap by hand: turn it slightly and pull it off the sprinkler. When removing caps, 

use care to prevent dislodging or damaging sprinkler ejector spring and fusible element. THE CAPS MUST BE REMOVED 

FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!

WARNING

Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agency. The sprinklers are 

designed to be installed in accordance with recognized installation standards. System design must be based on ESFR 

design guidelines described in the latest edition of Viking technical data, applicable FM Global Loss Prevention Data 

Sheets, the latest NFPA Standards, the latest standards of Verband der Sachversicherer (VdS), Loss Prevention Council 

(LPCB), the Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and 

standards whenever applicable. Deviation from the standards or any alteration to the sprinkler after it leaves the factory 

including, but not limited to: painting, plating, coating, or modification, may render the sprinkler inoperative and will 

automatically nullify the approval and any guarantee made by The Viking Corporation.

Summary of Contents for 14073AC

Page 1: ... plastics Cartoned expanded plastics Refer the Approval Charts and Design Criteria on pages 3 5 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and co...

Page 2: ...3 With the sprinkler con tained in the protective cap install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting DO NOT exc...

Page 3: ...al for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from s...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...uilding heights up to 30 ft 9 1 m the spacing allowed between sprinklers and or branch lines is 8 to 12 ft 2 4 to 3 7 m provided the area covered per sprinkler does not exceed the maximum 100 ft2 9 3 m2 allowed Refer to the Installation Standards for permissible deviations from the maximum sprinkler branch line spacing rules above to eliminate obstruc tions created by trusses and bar joists when u...

Page 6: ...pproved according to China GB Standard DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK503 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler...