background image

ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 3 of 6

Form No. F_120106    19.11.15    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

G. System design must be based on ESFR design guidelines described in applicable FM Global Loss Prevention Data Sheets, the 

latest standards of Verband der Sachversicherer, LPCB, the National Fire Protection Association, and the Authorities Having 

Jurisdiction. All requirements of recognized sprinkler system design standards apply to systems utilizing Viking ESFR Pendent 

Sprinklers.

5.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and spring assemblies to open 

the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to suppress 

the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency of 

inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of corrosion 

shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary, 

replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) 

and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers 

that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.

C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or other-

wise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should be 

given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping.

2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the 

replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response character-

istics. A fully stocked spare sprinkler cabinet should be provided for this purpose.

3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 

combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 

requirements.

7.  AVAILABILITY

Viking ESFR K16.8 Pendent Sprinkler VK503 is available through a network of domestic and international distributors. See The 

Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

NOTICE

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance 

of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and 

inspection requirements that must be followed.

Summary of Contents for 14073AC

Page 1: ... plastics Cartoned expanded plastics Refer the Approval Charts and Design Criteria on pages 3 5 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and co...

Page 2: ...3 With the sprinkler con tained in the protective cap install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting DO NOT exc...

Page 3: ...al for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from s...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...uilding heights up to 30 ft 9 1 m the spacing allowed between sprinklers and or branch lines is 8 to 12 ft 2 4 to 3 7 m provided the area covered per sprinkler does not exceed the maximum 100 ft2 9 3 m2 allowed Refer to the Installation Standards for permissible deviations from the maximum sprinkler branch line spacing rules above to eliminate obstruc tions created by trusses and bar joists when u...

Page 6: ...pproved according to China GB Standard DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK503 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler...