ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 5 of 6

Form No. F_120106    19.11.15    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

DESIGN CRITERIA - UL 

(Also refer to Approval Chart 1 on page 3.)

cULus Listing Requirements:

 

ESFR Pendent Sprinkler VK503 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest appropriate NFPA 

standards (including NFPA 13) for ESFR Pendent K16.8 (242 bar) Sprinklers, for: 

• 

Protecting rack storage of certain specified materials up to 35 ft (10.7 m) high in buildings with 40 ft (12.2 m) high ceilings with NO in-rack 

sprinklers.

 

• 

Protecting rack storage of certain specified materials up to 40 ft (12.2 m) high in buildings with 45 ft (13.7 m) high ceilings with one row of in-

rack sprinklers.

• 

NFPA 13 indicates the following for ESFR pendent sprinklers having a 16.8 nominal K-Factor: Position the deflector a maximum of 

14”

 (356 mm) 

and a minimum of 

6”

 (152 mm) below the ceiling.

• 

The minimum area of coverage allowed per sprinkler is 64 ft

2

 (5.8 m

2

) per NFPA 13.

Maximum Roof or Ceiling Slope:

 2 in 12 (167 mm/m or 9.5 degrees).

Sprinkler Position:

 Approved for use only in the pendent position. Align the deflector parallel with the ceiling or roof.

System Type:

 Wet systems only. 

Deflector Distance from Walls:

 At least 4” (102 mm) from walls, and no more than one-half the allowable distance permitted between sprinklers.

Clearance from Deflector to Top of Storage:

 At least 36” (914 mm).

Maximum Distance Between Sprinklers:

 The maximum area of coverage allowed per sprinkler is 100 ft

2

 (9.3 m

2

)**.

• 

For buildings over 30 ft (9.1 m) high, spacing between sprinklers and/or branch lines must be from 8 to 10 ft (2.4 to 3.1 m)**.

• 

For building heights up to 30 ft (9.1 m), the spacing allowed between sprinklers and/or branch lines is 8 to 12 ft (2.4 to 3.7 m), provided the 

area covered per sprinkler does not exceed the maximum 100 ft

2

 (9.3 m

2

) allowed**.

**Refer to the Installation Standards for permissible deviations from the maximum sprinkler/branch line spacing rules above, to eliminate obstruc-

tions created by trusses and bar joists when using ESFR sprinklers.

Minimum Area of Coverage:

 The minimum area of coverage allowed per sprinkler is 64 ft

2

 (5.8 m

2

).

Note:

 If the ceiling is beam and girder or panel construction, locate sprinklers in the bays rather than under the beams.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR 

Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest 

standards of VdS, NFPA, and any other Authorities Having Jurisdiction, and also with provisions of governmental 

codes, ordinances, and standards whenever applicable.

Approval Chart 1 (UL)

ESFR Pendent Sprinkler VK503 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

NPT Thread 

Size

Nominal 

K-Factor

Overall Length

Listings and Approvals

3,4 

(Refer also to Design Criteria on page 4.)

Inches mm

U.S. metric

2

Inches mm

cULus

5

NYC

6

VdS

LPCB

China 

Approval

14073

VK503

3/4”

--

16.8

242

2-7/8

73

A1

A1

--

--

--

--

14818

VK503

--

20 mm 16.8

242

2-7/8

73

A1

A1

--

--

--

--

20372

7

VK503

--

20 mm 16.8

242

2-7/8

73

B1

--

--

--

--

B1

Approved Temperature Ratings

A - 165 °F (74 °C) and 205 °F (96 °C)

B - 165 °F (74 °C)

Approved Finish

1 - Brass

Footnotes

1

 Base part number shown. For complete part number, refer to the price list.

2

 Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3

 This chart shows listings and approvals available at the time of printing. Other approvals may be in process. 

4

 Refer to the latest standards of NFPA 13.

Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

6

 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 41.

7

 Approved according to China GB Standard.

Summary of Contents for 14073AC

Page 1: ... plastics Cartoned expanded plastics Refer the Approval Charts and Design Criteria on pages 3 5 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and co...

Page 2: ...3 With the sprinkler con tained in the protective cap install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting DO NOT exc...

Page 3: ...al for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from s...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...uilding heights up to 30 ft 9 1 m the spacing allowed between sprinklers and or branch lines is 8 to 12 ft 2 4 to 3 7 m provided the area covered per sprinkler does not exceed the maximum 100 ft2 9 3 m2 allowed Refer to the Installation Standards for permissible deviations from the maximum sprinkler branch line spacing rules above to eliminate obstruc tions created by trusses and bar joists when u...

Page 6: ...pproved according to China GB Standard DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK503 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler...