ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 6 of 6

Form No. F_120106    19.11.15    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 2 (FM)

ESFR Pendent Sprinkler VK503 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

NPT Thread Size

Nominal K-Factor

Overall Length

FM Approvals

3,4 

(Refer also to Design Criteria below.)

Inches

mm

U.S.

metric

2

Inches

mm

14073

VK503

3/4”

--

16.8

242

2-7/8

73

A1

14818

VK503

--

20 mm

16.8

242

2-7/8

73

A1

20372

5

VK503

--

20 mm

16.8

242

2-7/8

73

B1

Approved Temperature Ratings

A - 165 °F (74 °C) and 205 °F (96 °C)

B - 165 °F (74 °C)

Approved Finish

1 - Brass

Footnotes

1

 Base part number shown. For complete part number, refer to the price list.

2

 Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3

 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. 

4

 FM Approved as a quick response pendent 

Non-Storage

 sprinkler and also FM Approved as a quick response pendent 

Storage

 sprinkler. Refer to 

Design Criteria below.

5

 Approved according to China GB Standard.

DESIGN CRITERIA - FM 

(Also refer to Approval Chart 2 above.)

FM Approval Requirements:

1.  Sprinkler VK503 is FM Approved as a quick response pendent 

Storage

 sprinkler as indicated in the FM Approval Guide. 

• 

For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheets 

2-0 and 8-9). 

2.  Sprinkler VK503 is also FM Approved as a quick response pendent 

Non-Storage

 sprinkler as indicated in the FM Approval Guide. 

• 

For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). 

FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling 

slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.

NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR 

Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest 

applicable FM Global Loss Prevention Data Sheets, including 2-0 and 8-9, applicable standards of NFPA, and any 

other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and standards 

whenever applicable.

Replaces Form No. F_120106 Rev 18.1.P65 

(Revised  China  Approval;  removed  19856.)      

Summary of Contents for 14073AC

Page 1: ... plastics Cartoned expanded plastics Refer the Approval Charts and Design Criteria on pages 3 5 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and co...

Page 2: ...3 With the sprinkler con tained in the protective cap install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting DO NOT exc...

Page 3: ...al for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the system from s...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...uilding heights up to 30 ft 9 1 m the spacing allowed between sprinklers and or branch lines is 8 to 12 ft 2 4 to 3 7 m provided the area covered per sprinkler does not exceed the maximum 100 ft2 9 3 m2 allowed Refer to the Installation Standards for permissible deviations from the maximum sprinkler branch line spacing rules above to eliminate obstruc tions created by trusses and bar joists when u...

Page 6: ...pproved according to China GB Standard DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK503 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler...

Reviews: