SPECIFICATIONS AND FEATURES
The VCC receives one of 3 signals from the adaptor board:
OFF, E
frequency, and
H
frequency.
OFF
STATE CRITERION
The VCC control signal is
OFF
whenever the voltage drive to the compressor relay is off.
H
(HIGH COOLING CAPACITY) STATE CRITERIA
The
VCC
control signal goes to the
H
frequency when any of the following conditions are
detected
:
•
The first compressor cycle after power restoration. The high capacity provides a faster
initial pull-down to control temperature
.
•
The compressor duty cycle exceeds DCHT, 90%. Once triggered, this mode persists until
the duty cycle drops below DCHX, 50%. A high external ambient increases the duty
cycle.
•
Compressor operation for more than 3 hours. The longest normal run time at 90
°
F is 2.5
to 3 hours. A longer run time implies the user activated the maximum refrigerate or
maximum freeze mode or there is an unusual cooling load. The mode persists until the
duty cycle drops below DCHX.
E
(EFFICIENT COOLING STATE CRITERION
The VCC control signal assumes the
E
state when none of the conditions above for the
H
state
are valid.
Note: Compressor Speed = Frequency x Motor Constant
10
Summary of Contents for DFSB483D
Page 1: ...VCSB483D DFSB483D DDSB483D COVER F90597...
Page 4: ...VCSB483D with ICE and WATER 4...
Page 5: ...CABINET AIR FLOW 5...
Page 6: ...MACHINE COMPARTMENT AIR FLOW 6...
Page 7: ...REFRIGERANT FLOW 7...
Page 8: ...WATER FLOW 8...
Page 27: ...VCSB483 WIRING DIAGRAM 27 27...
Page 28: ...VCSB483D WIRING DIAGRAM DISPENSER MODEL 28...
Page 38: ...CONTROL BOARD OPERATION 38...
Page 39: ...TROUBLESHOOTING 39...
Page 40: ...TROUBLESHOOTING con t 40...
Page 45: ...45...