WARNING
To avoid electrical shock which can cause severe personal injury or death, disconnect
power to refrigerator using power switch before servicing. Wires removed during
disassembly must be replaced on proper terminals to insure correct earth ground and
polarization. After servicing, reconnect power using power switch.
Evacuation and Charging
CAUTION: To avoid risk of fire, sealed
refrigeration system must be air free. To
reduce risk of air contamination, follow
evacuation procedures exactly.
NOTE:
Before opening any refrigeration
system, EPA regulations require refrigerant in
system to be captured for safe disposal.
Proper evacuation of sealed refrigeration system
is an important service procedure. Usable life
and operational efficiency greatly depends upon
low completely air, moisture and other non-
condensables are evacuated from sealed system.
Equipment Setup For Evacuation and Charging
5. After compound gauge (low side) drops
NOTE:
produce
e evacuating system until
7.
to
•
minutes, micron level stabilizes at
•
rises above 400 microns
•
s rapidly and does
ep 1.
Air in sealed system causes high condensing
temperature and pressure, resulting in increased
power requirements and reduced performance.
to approximately 29 inches gauge, open
valve “C” to vacuum thermocouple
gauge and take micron reading.
A high vacuum pump can only
Moisture in sealed system chemically reacts
with refrigerant and oil to form corrosive
hydrofluoric and hydrochloric acids. These
acids attack motor windings and parts, causing
premature breakdown.
a good vacuum if oil in pump is not
contaminated.
6. Continu
vacuum gauge registers 200 microns.
At 200 microns, close valve “A”
Before opening system, evaporator coil must be
at ambient temperature to minimize moisture
vacuum pump and allow micron reading
in system to balance. Micron lever will
rise.
If in 2
infiltration into system.
Evacuation:
To evacuate sealed refrigeration
system:
400 microns or below, system is ready
to be charges.
If micron level
1. Connect vacuum pump, vacuum tight
manifold set with high vacuum hoses,
thermocouple vacuum gauge and
charging cylinder as shown in
illustration. Evacuation should be done
and stabilizes, open valve “A” and
continue evacuating.
If micron reading rise
not stabilize, a leak still exists in system.
Close valve “A” to vacuum pump an
through I.D. opening of tubes not
through line piercing valve.
valve “C” to vacuum gauge. Invert
charging cylinder and open charging
cylinder valve “F” to add partial charge
for leak checking. With leak detector,
check manifold connections and system
for leaks. after locating leak, capture
refrigerant, repair leak, and begin at st
2. Connect low side line to compressor
process tube.
3. Connect high side line to drier/process
tube.
4. Evacuate both simultaneously. With
valve “C” and “F” closed, open all other
valves and start vacuum pump.
17
Summary of Contents for DFSB483D
Page 1: ...VCSB483D DFSB483D DDSB483D COVER F90597...
Page 4: ...VCSB483D with ICE and WATER 4...
Page 5: ...CABINET AIR FLOW 5...
Page 6: ...MACHINE COMPARTMENT AIR FLOW 6...
Page 7: ...REFRIGERANT FLOW 7...
Page 8: ...WATER FLOW 8...
Page 27: ...VCSB483 WIRING DIAGRAM 27 27...
Page 28: ...VCSB483D WIRING DIAGRAM DISPENSER MODEL 28...
Page 38: ...CONTROL BOARD OPERATION 38...
Page 39: ...TROUBLESHOOTING 39...
Page 40: ...TROUBLESHOOTING con t 40...
Page 45: ...45...