background image

Diagnostic Information

© Viking Range Corporation

SMR-0003

11

Error Code Detection

The microprocessor in the control continually monitors 

critical refrigeration system components for proper 

operation. If component parameters exceed normal 

operating specifications, an audible alarm will sound six 

(6) times every minute and the display will automatically 

flash the respective error code. If multiple errors are 

noted with the unit, the error codes will be displayed 

sequentially. See chart below for respective error codes 

descriptions and the potential causes of failure.

Error Code Detection Reference

Error Code

Error Code Reference

Potential Causes of 

Failure

E1

Compressor fault (high/

low amps)

1. Compressor wires 

disconnected.

2. Faulty compressor.

3. Faulty control.

4. Faulty compressor 

overload.

5. Faulty compressor 

PTC starter.

E2

Condenser fan motor 

fault (high/low amps)

1. Condenser fan motor 

wires disconnected.

2. Faulty condenser fan 

motor.

3. Faulty control.

E3

Evaporator thermistor 

“sensor B” fault (out-of-

range)

1. Disconnected wire 

causing open.

2. Shorted thermistor 

wires.

3. Faulty thermistor.

E4

Display thermistor 

“sensor A” fault (out-of-

range)

Resetting Error Codes:

Error Codes can only be reset by disconnecting and 

reconnecting the power supply to the unit.

Warning Alarm

The Tru Protect™ system will inform you if the unit is not 

functioning properly. It provides both visual and audible 

alerts if the temperature rises above or falls below the 

set temperature, if there is a power failure, or if the door 

is left ajar.

Door Ajar: If the door is left open for more than five 

1. 

(5) minutes, an audible alarm will sound three (3) 

times every 30 seconds and the LED light will flash 

green. This will stop as soon as the door is closed.

High and Low Temperature: If the unit reaches a 

2. 

temperature either above or below the set point 

temperature for more than one (1) hour, an audible 

alarm will sound six (6) times every minute and the 

LED will flash red. This will continue until the alarm 

is reset. The alarm may occur when changing set-

points in excess of 10 degrees F and/or high usage 

which is normal.

Power Failure: If the unit experiences a power 

3. 

failure, the LED will flash amber. This will continue 

until the alarm is reset. With a power failure, no 

audible signal is heard. The alarm may occur upon 

initial installation which is normal since the unit was 

run at the factory to verify quality.

Resetting the Alarms

Close door to reset Door Ajar alarm. Press the “ON/

OFF” button for approximately one (1) second to reset 

all other audible and display alarms.

NOTE:

  Although pressing the “ON/OFF” button will 

reset the alarms, the alarm will resume if the 

“alarm condition” still exists.

Show Room Mode

Show Room Mode is used mainly by salespersons and 

distributors. When the unit is in Show Room Mode, it will 

operate as if functioning normally; however, the internal 

components will not run.

Enabling Show Room Mode:

To enable Show Room Mode, press and hold the “ON/

OFF” button while performing a “Power On Reset” 

(POR), i.e. - disconnect and reconnect the power supply 

to the unit. When Show Room Mode is enabled, the 

compressor, condenser fan, internal fan(s), heater, 

reverse gas solenoid, and alarms are disabled. The 

display will show the last set point entered.

Disabling Show Room Mode:

To exit Show Room Mode, initiate a “Power On Reset” 

(POR) only.

Summary of Contents for DFUR144

Page 1: ...nal injury for improper service procedures done by an unqualified person Service SMR 0003 July 2008 DFRD144 DFUR143 DFUR144 DFUW144 DUAR143 DUAR144 DURD144 DUWC144 VUAR143 VUAR144 VURD144 VUWC144 2008...

Page 2: ...IT IS THE TECHNICIANS RESPONSIBILITY TO REVIEW ALL APPROPRIATE SERVICE INFORMATION BEFORE BEGINNING REPAIRS All safety information must be followed as provided in this document To avoid risk of elect...

Page 3: ...ic Refrigeration Tools 5 Installation 5 Electrical Requirements 5 Sealed System Basics 5 Diagnostic Information 6 Low Side leaks 6 High Side Leaks 6 Restricted Capillary Tube 6 Access Valves 6 Evapora...

Page 4: ...vary among the models listed in this service manual See chart below for unit specifications related to the model that you are servicing Wine Cellar Beverage Center Refrigerated Drawers Unit Specifica...

Page 5: ...h dry nitrogen gas 6 after final brazing This will flush out any air or moisture that may have entered the system before being absorbed into the ester oil Basic Refrigeration Tools The following list...

Page 6: ...be flushed thoroughly with nitrogen gas and evacuated to 50 microns before re charging High Side Leaks High side leaks consist of a break in the system at the condenser high side tubing drier or capil...

Page 7: ...the access valve on the compressor s process tube If any access valve is attached to the high side process tube remove it and then seal the tube by brazing before charging Charge the unit to specified...

Page 8: ...ade If this is not found replace the condenser fan Evaporator The evaporator uses evaporating refrigerant to remove heat from the inside of the unit ultimately making the interior cold The shape and s...

Page 9: ...ermistor is connected to the LED display and displays the temperature inside the unit on the display panel The following will happen in the event of one or both thermistors fail If the evaporator ther...

Page 10: ...d ALARMS OFF Steady Amber PRESS ON OFF Reset SET WARMER COLDER F C LIGHT OFF PRESS AND HOLD TruProtect System POWER FAILURE Flashing Amber HIGH LOW TEMP Red ALARMS OFF Steady Amber PRESS ON OFF Reset...

Page 11: ...or more than five 1 5 minutes an audible alarm will sound three 3 times every 30 seconds and the LED light will flash green This will stop as soon as the door is closed High and Low Temperature If the...

Page 12: ...e Service Mode press and hold the WARMER button while pressing the COLDER button four times within five seconds You cannot enable Service Mode while in Set Mode All system functions will remain in the...

Page 13: ...until the LIGHT button is pressed again 2 The light bulb is burned out Replace the light bulb and then press LIGHT button Door is closed but the light is still on inside of the unit 1 Did not press t...

Page 14: ...y minute Compressor fault high low amps 1 Compressor wires disconnected Check wiring diagram on back of unit and reconnect wires 2 Faulty compressor Replace compressor 3 Faulty control Replace control...

Page 15: ...times within five seconds LED is not displaying a steady green light on the display panel 1 Tru Protect was disabled Press and hold the SET button for five seconds NOTE Steady green light on the LED...

Page 16: ...ross the following Start winding Run winding See Compressor section Run Common Start terminals to compressor housing If run winding or start winding reads high to infinite resistance open replace comp...

Page 17: ...if dead short is found across fan terminals Replace fan if continuity is found between terminal and fan chassis Display Thermistor Disconnect and remove thermistor 1 from unit Use a known reference te...

Page 18: ...arter Remove overload from circuit and 1 allow 2 min to cool Check resistance between overload 2 terminals If terminals read open or dead short replace overload To avoid risk of electrical shock perso...

Page 19: ...te to the chair frame and slide out the baseplate enough to allow working room required see illustration below Remove Screws Slide out the mechanical baseplate Remove screws securing the mechanical ba...

Page 20: ...nd install the three sleeves where the carriage bolts will be located Mount the new compressor and install the three washers and lock nuts and tighten to 45 in lbs DO NOT REMOVE THE RUBBER PLUGS AT TH...

Page 21: ...screws that hold the baseplate to the 3 chair frame of the unit and slide out the mechanical baseplate Install sealed system access valve s and recover 4 refrigerant After recovering be sure to cap of...

Page 22: ...er for easier access to the lens 2 assembly Be careful not to disturb other wiring inside the unit Press in on the lens release tabs while 3 simultaneously prying the lens upward using a flat blade sc...

Page 23: ...OARD USER INTERFACE BOARD DOOR MAGNET REED SWITCH BLK WHT BLK YEL WHITE RED WHT BLK YEL YEL WHT RED BLU WHT YEL COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 L...

Page 24: ...CORD CONTROL BOARD USER INTERFACE BOARD DOOR MAGNET REED SWITCH WHT BLK YEL WHITE RED WHT BLK WHT BLU WHT YEL COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 LI...

Page 25: ...GNET REED SWITCH GND BLK BLK YEL WHITE BLK YEL GRN ORG RED BLK WHT RED COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 LINE NEU CHASSIS GND GRN USER INTERFACE BO...

Reviews: