background image

Disassembly

© Viking Range Corporation

SMR-0003

21

Thermistors

Disconnect power.

1. 

Remove back panel and lower shroud.

2. 

Disconnect the evaporator thermistor connector at 

3. 

the electronic controller.

Remove evaporator thermistor by removing the 

4. 

screw securing it.

Feed the thermistor wire out through the opening in 

5. 

the back of the unit.

Reverse the removal procedure for installation.

6. 

Lights

For Wine Cellars:

The wine cellars are equipped with two 6 watt tube lights 

located on the inside top of the cabinet. 

Replacing the Tube Light:

Disconnect power to the unit.

1. 

Remove the bulb from the channel in which it sits. 

2. 

Each light is fit snugly into the channel so you might 

need to use a screwdriver or knife to help loosen it.

Once the bulb is out of the channel, unplug it from 

3. 

the connector and set it aside.

Plug the new bulb into the connector and press 

4. 

the bulb snugly into the channel. You might need 

to press or tap firmly to place the bulb back in the 

channel.

Reconnect power to the unit and check to see if the 

5. 

light tube operates properly.

For Beverage Centers:

The beverage centers are equipped with a 15 watt light 

bulb located behind the display housing on the inside top 

of the cabinet.

Replacing the Light Bulb:

Disconnect power to the unit.

1. 

Unscrew the old light bulb located behind the display 

2. 

housing.

Set the old light bulb aside to discard.

3. 

Screw the new light bulb into place.

4. 

Reconnect power to the unit and check to see if the 

5. 

light bulb operates properly.

For Refrigerated Drawers:

The refrigerated drawers are equipped with two LED 

lights: one on the inside top of the drawer and one on 

the underside of the divider.

Condenser

Removing the condenser

Disconnect power to the unit.

1. 

Remove back panel and lower shroud.

2. 

Remove the screws that hold the baseplate to the 

3. 

chair frame of the unit and slide out the mechanical 

baseplate.

Install sealed system access valve(s) and recover 

4. 

refrigerant. After recovering, be sure to cap off the 

access valve(s) to prevent contamination of the 

system.

Remove the condenser fan by removing the 

5. 

four screws on the fan mounting bracket at the 

baseplate. The fan wire leads can be left connected. 

Set the fan assembly to the side out of the 

mechanical.

Remove the condenser fan shroud.

6. 

Un-braze capillary tube from drier assembly.

7. 

Un-braze high side tubing from the compressor.

8. 

Remove the condenser and drier assembly.

9. 

Installing the condenser

Reverse the removal procedure for installation. 

• 

Always install a new drier after opening the sealed 

• 

system.

Be sure to flush the system and evacuate to 50 

• 

microns before weight charging.

If contamination was found or determined, the 

• 

evaporator should also be replaced at this time.

Condenser Fan

Disconnect power to the unit.

1. 

Remove access panel and rear panel.

2. 

Remove the grille by removing the screws and 

3. 

disconnecting the wires to the rocker switch. Be sure 

to mark where these wires go for reassembly.

Take out the screws that secure the top of the 

4. 

electrical bracket located in the front of the 

mechanical area.

Remove the screws that secure the baseplate to the 

5. 

cabinet on the bottom of the unit.

Gently slide the mechanical out the back of the unit 

6. 

to gain access to the condenser fan.

Disconnect the neutral white wire lead (black ribbed 

7. 

wire) and hot wire lead (black smooth wire) from the 

wire harness.

Remove the condenser fan.

8. 

Reverse the removal procedure for installation.

9. 

To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit, unless test 

procedures require power to be connected. Discharge capacitor through a resistor before attempting to service. 

Ensure all ground wires are connected before certifying unit as repaired and/or operational.

Summary of Contents for DFUR144

Page 1: ...nal injury for improper service procedures done by an unqualified person Service SMR 0003 July 2008 DFRD144 DFUR143 DFUR144 DFUW144 DUAR143 DUAR144 DURD144 DUWC144 VUAR143 VUAR144 VURD144 VUWC144 2008...

Page 2: ...IT IS THE TECHNICIANS RESPONSIBILITY TO REVIEW ALL APPROPRIATE SERVICE INFORMATION BEFORE BEGINNING REPAIRS All safety information must be followed as provided in this document To avoid risk of elect...

Page 3: ...ic Refrigeration Tools 5 Installation 5 Electrical Requirements 5 Sealed System Basics 5 Diagnostic Information 6 Low Side leaks 6 High Side Leaks 6 Restricted Capillary Tube 6 Access Valves 6 Evapora...

Page 4: ...vary among the models listed in this service manual See chart below for unit specifications related to the model that you are servicing Wine Cellar Beverage Center Refrigerated Drawers Unit Specifica...

Page 5: ...h dry nitrogen gas 6 after final brazing This will flush out any air or moisture that may have entered the system before being absorbed into the ester oil Basic Refrigeration Tools The following list...

Page 6: ...be flushed thoroughly with nitrogen gas and evacuated to 50 microns before re charging High Side Leaks High side leaks consist of a break in the system at the condenser high side tubing drier or capil...

Page 7: ...the access valve on the compressor s process tube If any access valve is attached to the high side process tube remove it and then seal the tube by brazing before charging Charge the unit to specified...

Page 8: ...ade If this is not found replace the condenser fan Evaporator The evaporator uses evaporating refrigerant to remove heat from the inside of the unit ultimately making the interior cold The shape and s...

Page 9: ...ermistor is connected to the LED display and displays the temperature inside the unit on the display panel The following will happen in the event of one or both thermistors fail If the evaporator ther...

Page 10: ...d ALARMS OFF Steady Amber PRESS ON OFF Reset SET WARMER COLDER F C LIGHT OFF PRESS AND HOLD TruProtect System POWER FAILURE Flashing Amber HIGH LOW TEMP Red ALARMS OFF Steady Amber PRESS ON OFF Reset...

Page 11: ...or more than five 1 5 minutes an audible alarm will sound three 3 times every 30 seconds and the LED light will flash green This will stop as soon as the door is closed High and Low Temperature If the...

Page 12: ...e Service Mode press and hold the WARMER button while pressing the COLDER button four times within five seconds You cannot enable Service Mode while in Set Mode All system functions will remain in the...

Page 13: ...until the LIGHT button is pressed again 2 The light bulb is burned out Replace the light bulb and then press LIGHT button Door is closed but the light is still on inside of the unit 1 Did not press t...

Page 14: ...y minute Compressor fault high low amps 1 Compressor wires disconnected Check wiring diagram on back of unit and reconnect wires 2 Faulty compressor Replace compressor 3 Faulty control Replace control...

Page 15: ...times within five seconds LED is not displaying a steady green light on the display panel 1 Tru Protect was disabled Press and hold the SET button for five seconds NOTE Steady green light on the LED...

Page 16: ...ross the following Start winding Run winding See Compressor section Run Common Start terminals to compressor housing If run winding or start winding reads high to infinite resistance open replace comp...

Page 17: ...if dead short is found across fan terminals Replace fan if continuity is found between terminal and fan chassis Display Thermistor Disconnect and remove thermistor 1 from unit Use a known reference te...

Page 18: ...arter Remove overload from circuit and 1 allow 2 min to cool Check resistance between overload 2 terminals If terminals read open or dead short replace overload To avoid risk of electrical shock perso...

Page 19: ...te to the chair frame and slide out the baseplate enough to allow working room required see illustration below Remove Screws Slide out the mechanical baseplate Remove screws securing the mechanical ba...

Page 20: ...nd install the three sleeves where the carriage bolts will be located Mount the new compressor and install the three washers and lock nuts and tighten to 45 in lbs DO NOT REMOVE THE RUBBER PLUGS AT TH...

Page 21: ...screws that hold the baseplate to the 3 chair frame of the unit and slide out the mechanical baseplate Install sealed system access valve s and recover 4 refrigerant After recovering be sure to cap of...

Page 22: ...er for easier access to the lens 2 assembly Be careful not to disturb other wiring inside the unit Press in on the lens release tabs while 3 simultaneously prying the lens upward using a flat blade sc...

Page 23: ...OARD USER INTERFACE BOARD DOOR MAGNET REED SWITCH BLK WHT BLK YEL WHITE RED WHT BLK YEL YEL WHT RED BLU WHT YEL COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 L...

Page 24: ...CORD CONTROL BOARD USER INTERFACE BOARD DOOR MAGNET REED SWITCH WHT BLK YEL WHITE RED WHT BLK WHT BLU WHT YEL COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 LI...

Page 25: ...GNET REED SWITCH GND BLK BLK YEL WHITE BLK YEL GRN ORG RED BLK WHT RED COMM CONTROL BOARD DETAIL TOP VIEW ORG WHITE WHITE BLK YEL BLUE TAN J5 J8 J6 J4 J4A J7 LINE NEU CHASSIS GND GRN USER INTERFACE BO...

Reviews: