Fig ure 3: In stal la tion Guide lines

Fig ure 4: In stal la tion Guide lines - Lofts

NOTES:
1. Ac tual in stal la tions may re quire mul ti ple sprin klers. A sin gle sprin kler in stal la tion has been shown for clar ity.
2. For “ca the dral” ceil ing ap pli ca tions, in stall sprin klers in a sym met ri cal mir ror-image of Fig ure 3.
3. For sloped ceil ings over ar eas with ac cess open ings to ad ja cent up per level rooms or lofts, re fer to Fig ure 4.
4. For ar eas of cov er age be tween 16’ x 16’ and 18’ x 18’, with slopes be tween a 0/12 (0°) pitch  and a 6/12  (26.6°) pitch, use the

“Min i mum Wa ter Sup ply Re quire ments” for the next larger listed “sloped” in stal la tion.  Re fer to Ta ble 1 on page 145 c.

Form No. F_062395

Sprin kler 145 d

Jan u ary 27, 2000

Listed Areas of Cov er age

cor re spond to ar eas mea -

sured along ceil ing slope. (For 

sloped ceil ing in stal la tions,

ac tual floor cov er age will be

less than listed area.)

Re fer to Ta ble 1 on page 145 c

for Listed Areas of Cov er age.

Max i mum ceil ing slope = 

6/12 (26.6°).

Min i mum 8" lin tel for loft /

up per level ap pli ca tions.

Max i mum 6/12  (26.6°) pitch.

Re fer to Ta ble 1 on page 145 c.

TECH NI CAL DATA

Re places page 145 a-d, dated Sep tem ber 30, 1999
(added note to Fig ure 1).

HO RI ZON

®

 MODEL H-3

RES I DEN TIAL PEN DENT

SPRIN KLER, 3.8 K-FACTOR

OBSOLETE

Summary of Contents for HORIZON H-3

Page 1: ...eavy Duty Part No 10366W B Light Duty A 1 2 ratchet is required not available from Vi king Ideal for sprinkler cabinets 5 AVAILABILITYANDSERVICE Viking sprinklers are available through a network of domestic Canadian and in ternational distributors See the Yellow Pages of the telephone directory for a lo cal distributor listed under Sprinklers Automatic Fire or contact Viking Viking Technical Data ...

Page 2: ...ing and installation and to make sure the unit has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape ap plied and then reinstalled This is due to the fact that when the joint seal is damaged the sealing compound or tape is washed out of the joint H After testing repairing of all leaks and installation and painting of the ceiling the c...

Page 3: ...ESIDENTIAL PENDENT SPRINKLER 3 8 K FACTOR Sprinkler Temperature Classification Nominal Temperature Rating Maximum Ambient Temperature Allowed Temperature Identification Stamp Ordinary 165 F 74 C 100 F 38 C On Cover Intermediate 220 F 104 C 150 F 66 C On Cover Deflector Style NPT Thread Size Nominal K Factor Overall Length Base P N2 Inch mm U S metric1 Inch mm Pendent 1 2 15 3 8 5 5 2 9 16 65 1 094...

Page 4: ... 26 6 pitch use the Minimum Water Supply Requirements for the next larger listed sloped installation Refer to Table 1 on page 145 c Form No F_062395 Sprinkler 145 d January 27 2000 Listed Areas of Coverage correspond to areas mea sured along ceiling slope For sloped ceiling installations actual floor coverage will be less than listed area Refer to Table 1 on page 145 c for Listed Areas of Coverage...

Reviews: