INSTITUTIONAL SPRINKLERS K5.6

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 2 of 9

Form No. F_032319    20.01.03     Rev 20.1

© 2020 Viking Group Inc. All rights reserved

TABLE 1: ORDERING INFORMATION

INSTRUCTIONS: 

Choose a sprinkler style and base part number then,

 (1) add the suffix for the desired Finish

 (2) add the suffix for the desired Temperature Rating. 

(3) select an escutcheon plate and finish

4

.

Style

Sprinkler 

Base Part 

Number

SIN

Size

1: Available Finishes

2: Available Temperature Ratings

NPT

Inch

BSPT

mm

Description

Suffix

1

Nominal 

Rating

Max. Ambient 

Ceiling 

Temperature

3

Suffix

QR Pendent

19663

VK426

1/2

--

Chrome

F

165 °F (74 °C)

100 °F (38 °C)

C

QR Pendent

20110

VK426

--

15

Painted white

M-/W

205 °F (96 °C)

150 °F (65 °C)

E

QR HSW

22885

VK427

1/2

--

Painted gray

M-/RAL9006

QR HSW

22908

VK427

--

15

NOTE:

The escutcheons 

are available with the same 

finishes as the sprinklers.

3: Escutcheons

4

QR EC Pendent

19876

VK650

1/2

--

QR EC Pendent

20111

VK650

--

15

Description

Base Part Number

QR EC HSW

22884

VK651

1/2

--

3” (75 mm)

23196

QR EC HSW

22907

VK651

--

15

4” (100 mm)

23197

Examples

 

Sprinkler

19663MC/RAL9006

 = VK426 Quick Response Pendent with Painted gray Finish and 165 °F (74 °C) Nominal tempera-

ture rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the 

area will experience temperatures above the maximum ambient rating, you shall use a higher temperature-rated sprinkler.

Escutcheon

23196M/RAL9006

 = 3” Diameter Escutcheon with Painted gray finish.

Accessories
Sprinkler Wrench (see Figure 1): 

Socket Wrench: Part No. 22847MB

2

Retaining Flange (see Figure 1): 

Part Numer 10599 (includes 1/8” allen head set screw

5

)

Sprinkler Cabinet: 

Holds

 

Up to 6 sprinklers: Part number 01731A

Footnotes

1. 

Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.

2. 

Requires a 1/2” ratchet which is not available from Viking.

3. 

Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having 

Jurisdiction. Refer to specific installation standards.

4. 

The escutcheons are available with the same finishes as the sprinkler.

5. 

Requires a 1/8” allen wrench which is not available from Viking.

Figure 1: Sprinkler Accessories

Figure 2: Sprinkler Dimensions (Pendent and HSW)

3” (75 mm)

or

4” (100 mm)

1-3/4” (45 mm)

Sprinkler Wrench

Retaining Flange

1/4” (6 mm)

Nominal Pipe 

Engagement

7/16” (11mm)

1/8” 

Hex Screw

Summary of Contents for K5-6

Page 1: ...erage Flush sprinklers for extended areas of coverage up to 16 x 16 4 9 m x 4 9 m in Light Hazard occupancies only below smooth flat horizontal ceilings Refer to the Approval Chart and Design Criteria for requirements that must be followed NOTICE THE VIKING CORPORATION DISCLAIMS ANY RESPONSIBILITY FOR DAMAGES OR INJURY INCLUDING DEATH CAUSED BY THE OPERATION OR INOPERATION OF SPRINKLERS ARISING OU...

Page 2: ...96 QR EC HSW 22907 VK651 15 4 100 mm 23197 Examples Sprinkler 19663MC RAL9006 VK426 Quick Response Pendent with Painted gray Finish and 165 F 74 C Nominal tempera ture rating This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprink...

Page 3: ...1 03 Rev 20 1 2020 Viking Group Inc All rights reserved Figure 3 Sprinkler Components and Identification Horizontal Sidewall Pendent Pendent Deflector Sprinkler Type indicator Sprinkler Type indicator Horizontal Sidewall Deflector Sprinkler Data Location Stamped around the permimeter you will find Sprinkler Identification Number SIN K factor Coverage No mark for Standard Coverage and EC for Extend...

Page 4: ...orporation Flush sprinklers are decorative sprinklers and may be considered special purpose As such some Authorities may limit the use depending on the occupancy classification Refer to the Authority Having Jurisdiction prior to installation General Information The tamper resistant design of the Viking Institutional Sprinklers is dependant upon proper installation as outlined in this document as w...

Page 5: ...king on the protective cap Place the sprinkler wrench over the protective cap on the sprinkler body NOTE The wrench is uniquely designed to fit over the sprinkler cap and into the sprinkler in a specific alignment 6 Install the sprinkler into the fitting NOTE The Escutcheon plate MUST be tight against the ceiling or wall 7 Tighten the sprinkler to approximately 7 14 ft lbs 8 If desired use a level...

Page 6: ...sleeve 2 I D Cored Hole OR 2 Sch 40 Steel pipe sleeve Figure 5 Installation Dimensions Pendent Figure 6 Installation Dimensions HSW Upon activation the deflector actuates to approximately 7 8 22 mm beyond the sprinkler body 1 5 16 33 mm 1 4 6 mm 3 or 4 75 or 100 mm Face of fitting to finished surface of wall 7 8 22 mm Ensure the escutcheon plate is tight against the ceiling Ensure the escutcheon p...

Page 7: ... and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the installation standards and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced Whe...

Page 8: ...part number refer to Viking s current price schedule 2 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 3 Other colors are available upon request with the same Listings and Approvals as the standard colors LISTED FLOW RATES AND COVERAGE AREAS LIGHT HAZARD FOR Viking EXTENDED COVERAGE Institutional Sprinklers Spri...

Page 9: ...nkler must be installed in the horizontal sidewall position in fixed fire protection systems wet dry deluge or preaction systems Orient the top of the deflector parallel with the ceiling The wrench ear on the top of the Viking Institutional Style Quick Response Flush Horizontal Sidewall Sprinkler is marked with the word top Must be located with deflector 4 to 12 102 mm to 304 mm below the ceiling ...