Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
39
Single container systems with a pneumatic release device have a pilot cylinder that is activated
electrically. The control gas flows through a pilot line from the pilot cylinder to the pneumatic
release device for the extinguishing agent container and opens it.
4.1.2 Multi container systems
FIGURE 4-2: Multi container system
Multi container systems feature several extinguishing agent containers interconnected via a pilot
line. They are required, for example, if a large protection zone must be protected.
In multi container systems without a pneumatic release device, the first extinguishing agent con-
tainer (master) is actuated electrically in the same way as in single container systems (and option-
ally also manually). All other extinguishing agent containers (slaves) are opened pneumatically
through a pilot line.
Multi container systems with a pneumatic release device feature a pilot cylinder that is triggered
electrically. The control gas flows through a pilot line from the pilot cylinder to the pneumatic
release devices for the extinguishing agent containers and opens them.
In contrast to single container systems, the extinguishing agent initially flows from the hose
through check valves into a manifold if a multi container system is actuated. From there, the extin-
Use single container systems without a pilot cylinder only if you have ensured that the extinguishing
agent that flows out does not pose a danger to people.
Summary of Contents for Oxeo
Page 1: ...Installation and Maintenance Manual Oxeo Inert Gas Extinguishing System...
Page 10: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 4...
Page 32: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 26...
Page 42: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 36...
Page 134: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 128...
Page 148: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 142...
Page 156: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 150...
Page 176: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 170...
Page 206: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 200...
Page 220: ...Inst and Maint Manual Oxeo PR LCP F_101921 Rev 02 10 2022 en 214...
Page 221: ...Oxeo PR LCP 10 2022 en 215 15 SafetyDataSheet IG 01 Argon...
Page 228: ...Oxeo PR LCP 10 2022 en 222...
Page 229: ...Oxeo PR LCP 10 2022 en 223 16 SafetyDataSheet IG 100 Nitrogen...
Page 236: ...Oxeo PR LCP 10 2022 en 230...
Page 237: ......