TECHNICAL DATA

QUICK RESPONSE 

EXTENDED COVERAGE 

CONCEALED HSW 

SPRINKLER VK680 (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Form No. F_050611    18.10.25     Rev 17.1.P65

Page 4 of 5

Sprinkler Base

 

Part Number

1

NPT Thread Size

Nominal K-Factor

Maximum Water

 

Working Pressure

Overall Length

 

(Sprinkler Body)

Inches

mm

U.S.

metric

2

psi (bar)

Inches

mm

17114AC

3/4

--

8.0

115.2

175 (12)

2

51

NOTICE - Product Below - ONLY for CCCF Approval

20379AC

--

20 mm

8.0

115.2

175 (12)

2

51

Approval Chart

QREC Concealed HSW Sprinkler VK680

For Light Hazard Occupancies Only.

 

For installation below smooth, flat, horizontal ceilings only.

Maximum Areas of 

Coverage

(Width x Throw)

Minimum Water Supply Requirements

4

Sprinkler Distance

 

Below the Ceiling

Listings and Approvals

3

(Refer also to Design Criteria on page 4.)

cULus

5

NYC

14’ x 22’ (4.3 m x 6.7 m)

31 gpm @ 15.0 psi (117.3 L/min @ 1.04 Bar)

Must be installed 

with the centerline 

of the sprinkler 

4-3/8” to 12-3/8” 

(112 to 

314 mm) below the 

ceiling.

AX1

See Footnote 6.

AX1

16’ x 16’ (4.9 m x 4.9 m)

26 gpm @ 10.6 psi (98.4 L/min @ 0.73 Bar)

AX1

AX1

16’ x 18’ (4.9 m x 5.5 m)

29 gpm @ 13.1 psi (109.8 L/min @ 0.91 Bar)

AX1

AX1

16’ x 20’ (4.9 m x 6.1 m)

32 gpm @ 16.0 psi (121.1 L/min @ 1.1 Bar)

AX1

AX1

16’ x 22’ (4.9 m x 6.7 m)

36 gpm @ 20.3 psi (136.3 L/min @ 1.4 Bar)

AX1

AX1

18’ x 18’ (5.5 m x 5.5 m)

 33 gpm @ 17.0 psi (124.9 L/min @ 1.2 Bar)

AX1

AX1

18’ x 20’ (5.5 m x 6.1 m)

 36 gpm @ 20.3 psi (136.3 L/min @ 1.4 Bar)

AX1

AX1

18’ x 22’ (5.5 m x 6.7 m)

 40 gpm @ 25 psi (151.4 L/min @ 1.72 Bar)

AX1

AX1

14’ x 24’ (4.3 m x 7.3 m)

34 gpm @ 18.1 psi (128.7 L/min @ 1.25 Bar)

4-3/8” (112 mm)

to 6-3/8” (162 mm)

AX1

--

16’ x 24’ (4.9 m x 7.3 m)

39 gpm @ 23.8 psi (147.6 L/min @ 1.64 Bar)

AX1

--

14’ x 24’ (4.3 m x 7.3 m)

35 gpm @ 19.2 psi (132.5 L/min @ 1.32 Bar)

6-3/8” (162 mm) 

to 12-3/8” (314 mm)

AX1

--

16’ x 24’ (4.9 m x 7.3 m)

40 gpm @ 25 psi (151.4 L/min @ 1.72 Bar)

AX1

--

Sprinkler Temperature 

Rating

A  - 165 °F (74 °C)

Cover Assembly

 

Temperature Rating

X - 135 °F (57 °C) cover 16207

1

Cover Plate Finishes

1 - Polished Chrome, Painted White

7

, Painted Ivory

7

, or Painted Black

7

Footnotes

1

 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.

2

 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3

 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any 

additional approvals. 

4

 For areas of coverage smaller than shown, use the “Minimum Water Supply Requirement” for the next larger area listed. Flows and pressures listed 

are per sprinkler.

5

 Listed by Underwriter’s Laboratories, Inc. for use in the U.S. and Canada. cULus Listings are limited to Light Hazard occupancies with smooth, flat, 

horizontal ceilings only. Always install horizontal sidewall sprinkler VK680 with the top of the sprinkler element oriented parallel with the ceiling. Refer 

to Figure 3 on page 4. 

6

 Meets New York City requirements, effective July 1, 2008.

Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. 

Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.  

  NOTE:

 Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.

Summary of Contents for VK680

Page 1: ...Listed Category VNIV CCCF Approved Approved by the China Certification Center for Fire Products CCCF Refer to the Approval Chart and Design Criteria on this Technical Data Page for cULus Listing requirements that must be followed 3 TECHNICAL DATA Specifications Available since 2011 Minimum Operating Pressure 7 psi 0 5 bar Maximum Working Pressure 175 psi 12 Bar Factory tested hydrostatically to 50...

Page 2: ...ble since 2010 B Head Cabinet Wrench Part Number 16267 available since 2010 C Optional Large Concealed Cover Plate Installer Tool Part No 14867 available since 2007 Requires a ratchet not available from Viking Ideal for sprinkler cabinets Sprinkler Cabinet Part No 01731A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions when the...

Page 3: ...its may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 Part number shown is the base part number For complete part number refer to current Viking price list schedule Figure 2 Sprinkler VK680 Installation and Correct Use of Wrench The internal design of the sprinkler wrench is shaped to fit ov...

Page 4: ...4 L min 1 72 Bar AX1 AX1 14 x 24 4 3 m x 7 3 m 34 gpm 18 1 psi 128 7 L min 1 25 Bar 4 3 8 112 mm to 6 3 8 162 mm AX1 16 x 24 4 9 m x 7 3 m 39 gpm 23 8 psi 147 6 L min 1 64 Bar AX1 14 x 24 4 3 m x 7 3 m 35 gpm 19 2 psi 132 5 L min 1 32 Bar 6 3 8 162 mm to 12 3 8 314 mm AX1 16 x 24 4 9 m x 7 3 m 40 gpm 25 psi 151 4 L min 1 72 Bar AX1 Sprinkler Temperature Rating A 165 F 74 C Cover Assembly Temperatu...

Page 5: ...ween sprinklers The distance shall be measured perpendicular to the wall The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage sidewall spray sprinklers must be followed NOTE Concealed sprinklers must be installed in neutral or negative pressure plenums only IMPORTANT Always refer to Bulletin Form No F_091699 Care and Handling of Sprinklers Also refer to Form ...

Reviews: