SPECIFIC APPLICATION
WINDOW SPRINKLERS
(K5.6)
TECHNICAL DATA
Form No. F_042519 21.09.28 Rev 21.3
© 2021 Viking Group Inc. All rights reserved
Page 2 of 10
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
TABLE 1: SPRINKLER ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
SIN
Sprinkler
Base Part
Number
Style
Size
1: Finishes
2: Temperature Ratings
NPT
Inch
BSPT
mm
Description
Suffix
1
Sprinkler
Temperature
Classification
Nominal Rating
Max. Ambient
Ceiling
Temperature
2
Bulb
Color Suffix
VK960
23832
Pendent VSW
1/2
--
Brass
A
Ordinary
155 °F (68 °C) 100 °F (38 °C) Red
B
VK960
23829
Pendent VSW
--
15
Chrome
F
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
E
VK962
23834
HSW
1/2
--
White Polyester M-/W
Corrosion Resistant Sprinkler Finish
: ENT
Example: 23832JNE = VK960,
200 °F (93 °C) Temperature Rated
Sprinkler with an ENT
3,4
finish.
VK962
23831
HSW
--
15
Black Polyester
M-/B
ENT
3,4
JN
Accessories
Sprinkler Wrenches and tools:
Standard Wrench Part Number: 23559MB
Sprinkler Cabinet:
Holds up to 6 sprinklers: Part number 01724A
Footnotes
1.
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2.
Based on NFPA 13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific
installation standards.
3.
cULus Listed as corrosion resistant.
4.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Figure 1: Sprinkler Dimensions (Pendent VSW and HSW)
2-7/16”
(62 mm)
Top View
1-15/16”
(49 mm)
1-1/2”
(40 mm)
Figure 1: Sprinkler Wrench
Top View