VIKING TECHNICAL SUPPORT 1.800.908.0884
4 3
UL LEARN
SENSOR 1
Appendix (C)
STEP 2
Turn ON the UL ADV
Feature:
• Toggle the “Diagnose”
button until you see
UL ADV
on the LCD Display.
• Default setting is OFF.
• Press and hold the “Stop”
button.
• Toggle the “Diagnose”
button once.
• The feature should now be
displayed as “ON”.
STEP 1
Connect the Monitored Sensor to the Viking control board input terminals “UL” and
“GND” as illustrated.
UL ADV
OFF
24VDC (may not be required on all sensors)
10K (Sensor’s Monitored Terminals)
UL ADV Feature
IMPORTANT REQUIREMENTS:
• The installed sensor MUST be
“10K Resistor Based”.
• Only u
se this feature if
ALL sensors connected to the UL input terminal are desired
to reverse the gate all the way to the OPEN LIMIT position.