12
Approvals and Codes
(continued)
Homologations et codes
(suite)
High Altitude Installations
U.L. Listed gas appliances are tested and approved without
requiring changes for elevations from 0 to 2,000 feet in the
U. S. A. and in Canada.
When installing this appliance at an elevation above 2,000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. or 10% for elevations
between 2000 and 4500 in Canada. If the heating value of
the gas has been reduced, these rules do not apply. To
identify the proper orifice size, check with the local gas utility.
If installing this appliance at an elevation above 4,500 feet
(in Canada), check with local authorities.
Installation à haute altitude
Les appareils à gaz homologués U.L. ont été testés et
approuvés pour être utilisés sans modification à des altitudes
comprises entre 0 et 610 mètres (0 et 2 000 pieds) aux
États-Unis et au Canada.
Si cet appareil est installé à une altitude supérieure à 610
mètres, il peut s’avérer nécessaire de réduire l’admission
du gaz en diminuant l’ouverture de l’orifice du brûleur. Le
débit calorifique doit être réduit de 4 % tous les 305 mètres
(1 000 pieds) au-dessus de 610 mètres d’altitude (2 000
pieds) aux États-Unis ou de 10 % entre 610 et 1 372 mètres
d’altitude (2 000 et 4 500 pieds) au Canada. Si le pouvoir
calorifique du gaz a été réduit, ces règles ne s’appliquent
pas. Pour connaître l’ouverture de l’orifice qui convient,
consultez le service local de distribution de gaz.
Si cet appareil est installé à une altitude supérieure à 1.370
mètres (au Canada), consultez les autorités locales.