1
Refrigerating Specialties Division
STOP / STRAINER VALVE
Port Size 13-100mm (1/2”- 4”)
FOR AMMONIA, R12, R22, R502
AND OTHER COMMON REFRIGERANTS
FEATURES
BULLETIN 86-00
March 2003
Installation, Service and Parts Information
I S O 9 0 0 1 C E R T I F I E D
• Handwheel or Seal Cap
• Replaceable PTFE seat disc
• Full-ported angular seat allows washing action
• Positive shut-off
• Low pressure drop
• 50 & 100 mesh stainless steel screen
• Stainless steel stem with positive back seating
• Drain connection for safe cleaning
• Maximum Safe Working Pressure 400 PSIG
• Fluid Temperature Range -65°F to +350°F
Fig. 1
SCREEN
ASSEMBLY
DRAIN CONNECTION
STAINLESS
STEEL STEM
HANDWHEEL
SEAL CAP
ANGULAR SEAT
PTFE SEAT
DISC
Description
The Refrigerating Specialties combination stop/strainer
shut-off valves are designed to provide all the benefits of a
typical valve and strainer assembly within a single valve
body. This unique combination valve decreases the
effects of pressure drop in a system by eliminating the
need for a separate strainer, while reducing system and
installation costs.
Warranty
All Refrigerating Specialties products are warranted against defects in
workmanship and materials for a period of one year from date of shipment
from originating factory. This warranty is in force only when products are
properly installed, field assembled, maintained, and operated in use
and service as specifically stated in Refrigerating Specialties Catalogs
or Bulletins for normal refrigeration applications, unless otherwise
approved in writing by Refrigerating Specialties Division. Defective
products, or parts thereof returned to the factory with transportation
charges prepaid and found to be defective by factory inspection will be
replaced or repaired at Refrigerating Specialties option, free of charge
F.O.B. factory. Warranty does not cover products that have been aftered,
or repaired in the field; damaged in transit, accidents, misuse, or abuse.
Products disabled by dirt or other foreign substances will not be
considered defective.
The express warranty above constitutes the only warranty of Refrigerating
Specialties products, and is in lieu of all other warranties, expressed or
implied, written or oral, including any warranty of merchantability or
warranty of fitness for a particular purpose and in no event is Refrigerating
Specialties responsible for any consequential damages of any nature
whatsoever. No employee, agent, dealer or other person is authorized
to give any warranties on behalf of Refrigerating Specialties nor to
assume for Refrigerating Specialties any other liability in connection
with any of it products.
Safe Operation (See also Bulletin RSB)
People doing any work on a refrigeration system must be qualified
and completely familiar with the system and the Refrigerating
Specialties Division valves involved, or all other precautions will
be meaningless. This includes reading and understanding
pertinent Refrigerating Specialties Division product Bulletins and
Safety Bulletin RSB prior to installation or servicing work.
Where cold refrigerant liquid lines are used, it is necessary that certain
precautions be taken to avoid damage that could result from liquid
expansion. Temperature increase in a piping section full of solid liquid
will cause high pressure due to the expanding liquid that can possibly
rupture a gasket, pipe or valve. All hand valves isolating such sections
should be marked, warning against accidental closing, and must not be
closed until the liquid is removed. Check valves must never be installed
upstream of solenoid valves, or regulators with electric shut-off, nor
should hand valve upstream of solenoid valves or downstream of check
valves be close until the liquid has been removed. It is advisable to
properly install relief devices in any section where liquid expansion
could take place.
Avoid all piping or control arrangements that might produce thermal or
pressure shock. For the protection of people and products, all
refrigerant must be removed from the section to be worked on before a
valve, strainer, or other device is opened or removed. Flanges with
ODS connections are not suitable for ammonia service.
310604
Summary of Contents for VSM 71-701
Page 1: ...1 VPN 35391S February 2006 Rev 05 Price 60 00...
Page 2: ...2...
Page 20: ...20...
Page 52: ...53 Pre Start Up Check List...
Page 99: ...99 Recommended Spare Parts List...
Page 104: ...104 Gate Rotor...
Page 110: ...110 Main Rotor VSS...
Page 112: ...112 Main Rotor VSR...
Page 114: ...114 Slide Valve Cross Shafts and End Plate...
Page 118: ...118 Capacity Slide Volume Slide Carriage Assembly Slide Valve Carriage Assembly...
Page 134: ...134 Miscellaneous Frame Components VSS Screw Compressor VSR Mini Screw Compressor...
Page 138: ...138 C FlangeAdapter Components 630 620 610 640 601 641 630 601 620 610 640 641 642 650 651...
Page 140: ...140 Replacement Parts Tools...
Page 144: ...144 GaterotorAssembly...
Page 148: ...148 Main Rotor Slide Valve Cross Shafts and End Plate Models 71 401 Only Counter clockwise...
Page 152: ...152 Main Rotor Slide Valve Cross Shafts and End Plate Model 501 701 Only Clockwise...
Page 154: ...154 Volume Ratio Capacity Slide Carriage Assembly Slide Valve Carriage Assembly...
Page 158: ...158 Miscellaneous Frame Components Model VSM 501 701 Model VSM 71 401...
Page 160: ...160 Replacement Parts Accessories Housing Accessories C Flange Assembly...
Page 166: ...166 Haight Pumps...
Page 170: ...3 Refrigerating Specialties Division...
Page 236: ......
Page 237: ......
Page 238: ......
Page 243: ......
Page 244: ...168...