38
Impulse counters can be configured to start from any initial amount of impulses. To do that –
enter initial amount of Impuls for “Discrete IN” channel and Set it to data logger (see in Green
color marked group in
In some cases is needed to have changed values (not counted Impulses), to do that use “Impulse
multiplier” (range from 0.001 to 1000) (see in Blue color marked group in
). For example,
if Impulse counter takes impulses from water meter after each Liter of the water and you need to
calculate cubic meters of the water, so you add “Impulse multiplier” = 0.001 and result of Current
value will have value in cubic meter’s dimmension.
With enabled “Alarm state”, discrete channels can be used to indicate Alarm status and depending
on Alarm status condition (Open, Close or in Both cases), data logger will make a record to Event
archive (see chapter
7.15
Data storing to archive [Archives]) and Alerts module will send warning
SMS Alert on Discrete Alarms).
If you just need to view status of Discrete channels select Discrete input mode. Like in other
modes, by enabling archiving you can store changes of discrete channels to archive (choose when
to save – on Open, on Close or in Both cases) how to manage Events see chapter
7.15
Data
storing to archive [Archives], and to view see chapter
8.6
Discrete inputs log
[Archives>Values>Discrete inputs].
Alarm mode will not work if “Impulse counting” mode is enabled!
“Clear” button will clear current Value, Initial amount and Impulse quantity fields
– use it carefully.
7.4
Discrete outputs [Discrete outputs]
Performed functions:
Turning of relative Discrete Outputs ON and OFF over GPRS, Ethernet;
Archiving time of changed Discrete outputs states and new state;
Storing states to energy independent memory and restore their last status, after power-on.
Configurable parameters:
Enabling/Disabling Discrete Output usage;
Changes archiving Enabling/Disabling
Enabling/Disabling restoring of last state after power off;
Impulse duration in ms.
On/Off buttons are showing current stage of each Discrete OUT channels. By clicking on button,
you can permanently change status, or using Impulse buttons - send impulse of given interval
Summary of Contents for MX-7
Page 1: ...2 ...
Page 4: ...5 9 6 USB cable 85 9 7 Installing VILTRUS USB driver 85 9 8 TCP IP settings 87 ...
Page 22: ...23 see Pic 6 3 6 V 5 V 6V 8 V 10 V Pic 6 Power for external device DIP switch ...
Page 53: ...54 Pic 48 Routing configuration example ...
Page 54: ...55 Pic 49 Routing screenshots ...
Page 59: ...60 2 Set COM port number UART port must be configured and assigned to COM client on ...
Page 66: ...67 Pic 61 Setting up RAY 1 as External module by example ...
Page 75: ...76 Pic 71 Records in archives section Archives Configutation ...