6.2.1 Speed setting
The speed is set using the potentiometer built into the unit or otherwise using the REB ECOWATT
®
or
CVF remote control.
By default
, the unit is set to its maximum speed, in bold in the table below. The
potentiometer built into the unit is used to modify the turbine’s speed to set the air volume.
Potentiometer graduation and speed correlation chart
JBRB ECOWATT
®
Single-phase - 04 to 22
Potentiometer
graduation
Voltage (V) applied to motor
0-10V input
JBRB ECOWATT
®
04
JBRB ECOWATT
®
06
JBRB ECOWATT
®
10
JBRB ECOWATT
®
22
0
0
0rpm
0rpm
0rpm
0rpm
2
2
700rpm
600rpm
540rpm
475rpm
4
4
1,400rpm
1,200rpm
1,080rpm
950rpm
6
6
2,100rpm
1,800rpm
1,620rpm
1,425rpm
8
8
2,800rpm
2,400rpm
2,160rpm
1,900rpm
10
10
3,500rpm
3,000rpm
2,700rpm
2,375rpm
JBRB ECOWATT
®
Single-phase - 30 to 82
Potentiometer
graduation
Voltage (V) on controller
terminal 9
JBRB ECOWATT
®
30
JBRB ECOWATT
®
38
JBRB ECOWATT
®
48
JBRB ECOWATT
®
70
JBRB ECOWATT
®
82
0
0
200rpm
200rpm
200rpm
200rpm
200rpm
2
1
610rpm
530rpm
460rpm
460rpm
430rpm
4
2
1,020rpm
855rpm
720rpm
720rpm
660rpm
6
3
1,430rpm
1,180rpm
980rpm
980rpm
890rpm
8
4
1,840rpm
1,500rpm
1,240rpm
1,240rpm
1,120rpm
10
5
2,250rpm
1,830rpm
1,500rpm
1,500rpm
1,350rpm
JBRB ECOWATT
®
Three-phase - 30 to 92
Potentiometer
graduation
Voltage (V) on controller
terminal 10
JBRB ECOWATT
®
30
JBRB ECOWATT
®
38
JBRB ECOWATT
®
48
JBRB ECOWATT
®
70
JBRB ECOWATT
®
92
0
0
200rpm
200rpm
200rpm
200rpm
200rpm
2
2
610rpm
530rpm
460rpm
460rpm
460rpm
4
4
1,020rpm
855rpm
720rpm
720rpm
720rpm
6
6
1,430rpm
1,180rpm
980rpm
980rpm
980rpm
8
8
1,840rpm
1,500rpm
1,240rpm
1,240rpm
1,240rpm
10
10
2,250rpm
1,830rpm
1,500rpm
1,500rpm
1,500rpm
For information: The airflow is proportional to the rotation speed.
Q
v2 =
Q
v1 x(N2/N1)Where N is the rotation speed.