F u n c t i o n
A d d r e s s
R e a d / W r i t e
D e s c r i p t i o n
A c c e p t e d v a l u e
Fire Alarm
10042
R
Fire alarm
0 or 1
0=Normal, 1=Alarm
Antifrost on
water coil
10057
R
Low water temperature (<7°C)
0 or 1
0=Normal, 1= alarm
C O IL ST A T U S
Signal 0-10V
of the valve
actuator
30119
R
Hot water signal ( 0-10V) Y1
0..100
Value: 0..100 means 0,0V .. 10.0V.
30121
R
Cold water signal ( 0-10V) Y3
0..100
Value: 0..100 means 0,0V .. 10.0V.
Saison/change
over
10017
R
read position status (input DI4)
0 or 1
0= hot control position ; 1= cold control position
T EM P ER A T U R E SET P O INT
Supply air
position set
point
40001
R/W
Set point température in 'constant supply air Temperature'
0…999
value: 0..+999 means 0 .. +99,9°C; 0 =off
Saison/change
over
40230
R/W
Change over control mode 0=heating mode, 1=cooling
mode, 2=auto
0, 1 or 2
W O R K ING T IM E
Fans working
time hours
30 004
R
Running time of supply air fans
0…999999
30005
R
Running time of exhaust air fans (ASR)
0…999999
Value: 0 .. 999999
The complet list could be load on our web site or on Etool / help/corrigo variable list.
1 0 . 2 B a c n e t c o m m u n i c a t i o n p r o t o c o l e f o r B M S c o m m u n i c a t i o n
B A C n e t M S/ T P O N p o r t 2 – R S4 8 5
(BACnet MS/TP)
P1 RxTx
TCP/IP P/
B B 50
A 51 N 52 E 53 B 60 A 61 N 62 E 63
P2 RxTx
CORRIGO
P 1
P 2
The regulator CORRIGO has 2 communication ports RS485 (to use with
a cable STP), the port2 is dedicated by default to the communication in
BACnet MS / TP, but the function must be activated to be able to work.