Advanced confi guration in expert mode:
Used to read the message of the alarm indicated on the main screen and program the clock
Advance parameter
menu navigation
buttons :
E-DSP display
Confirm :
Read the alarm
message :
Go back to previous screen :
Single air flow unit
2012-11-12
System: Normal Fonc.
C: 24.0C /R: 17.8C
sub menu :
Alarme screen
6.Filter pressure switch
27 Aou 14:33 Class:C
1 screen :
Running mode
Temperature
Air control
Time settings
Access rights
Menu
Main screen
Menu screen
Settings menu access
Advanced settings
Single air flow unit
2012-11-12
System: Normal Fonc.
C: 24.0C /R: 17.8C
21.4°C
2012-06-26 14:02
25 00 m3 /h
Run mode : ON
Alarm ON
8.2 Constant fl ow operation (CAV)
CAV
Recommended mode to directly obtain the desired fl ow in an installation.
The speed of the fan is defi ned to provide an accurate fl ow and maintain it at a constant
level.
The supply air fl ow is controlled. The "Low Speed" and "High Speed" fl ow set points are
adjusted independently in m
3
/h in the ETD command control.
The pressure transmitter measures the diff erential pressure on the fan suction chamber. The fl ow arising
from the pressure measurement is calculated by the controller, according to a coeffi cient K particular to
the fan.
The change-over between the various set points will be completed manually or automatically by time pro-
gramming.
The PI adjustment loop of the fan maintains the set point by adjusting the fan.
A third "night speed" set point may be entered via the control panel. The value as a % corresponding to the
percentage of the maximum fan speed will be used during night cooling (see corresponding function).
A timeout of 60 seconds is integrated into the programme to guarantee that the heating elements are pro-
tected in the event that a unit stop request is made.
Functional confi guration on ETD
Access to the simplifi ed confi guration menu (via password 1111) enables:
• Low Speed and High Speed fl ows of the fan to be selected.
• The night set point value of the fan.
CAV
CAV toevoer
Low speed
High speed
Night speed
800 m3/h
400 m3/h
80%
Parameter
Previus
screen
Next screen
Ventilation mode
The selection of this mode in this installer menu automatically confi gures the user menu screen. The user
can therefore change the operating mode of the unit without touching the settings.