8.5 Temperature adjustment
8.5.1 Maintaining a constant supply temperature
Parameter
Constant
supply air T°C
Heating mode
The temperature is adjusted by comparing the blown air temperature
and the set point value confi gured with the console.
This is the default factory setting, and the blown air temperature sensor
is provided and should be attached to the supply duct.
The user has the option of a +/-3°C override in relation to this initial set point from the main screen.
8.5.2 Maintaining a constant room or return temperature
Parameter
Cascade connected
extract air
temperature control
Heating mode
The supply is adjusted in cascade mode with the room or return temper-
ature.
The discrepancy between the room or return temperature and the set
point determines the supply temperature. A room or extract air sensor
must be added.
The adjustment is a response to a request to maintain a room or return
temperature, by reducing the temperature gained. This is included in an
admissible range of 12 to 30C°, controlled by a supply sensor provided,
to be attached to the duct.
The user has the option of a +/-3°C override in relation to this initial set point from the main screen.
8.5.3 Adapting the temperature set point according to the exterior temperature
Parameter
Constant supply air T°C with
outdoor T°C compensation
Heating mode
Outdoor air temperature
Compensation curve
Supply air
T°C setpoin
t
-30
-20
-10
0
10
14
20
18
22
26
The adjustment operates in a similar way to the 1st case.
Instead of a single temperature set point, a compensation curve is defi ned by the factory by 8 set points.
The supply set point is thus adapted in relation to this curve, and the override of more or less 3°C pos-
sible from the main screen continues to be accessible. The necessary external temperature sensor is
provided and assembled, and the blown air temperature sensor is provided and should be attached to
the supply duct.