NT-50906901-KSDR-ECOWATT-48-88-120-AN-170907
67/68
ENGLISH
10.9 Replacement of the CORRIGO controller battery
When the low battery alarm appears and the red indicator lights up, that means that the backup battery to
save the memory and real time clock is too low.
The procedure for changing the battery is described below.
A capacitor makes it possible to save the memory and operate the clock for about 10 minutes after the
current has been cut.
If the battery is changed in under 10 minutes, there is no need to reload the programme and the clock
continues to operate as normal.
The replacement battery is of the CR2032 type.
• Press the clip on each side of the panel with a
small screwdriver to loosen the base lid.
• Hold the base and remove the lid.
• Grip the battery and softly pull upwards until
the battery is removed from its enclosure.
• Take a new battery and slide it into the sup-
port. Pay attention to the direction of assembly
of the battery in order to respect polarity.
11. WASTE MANAGEMENT
11.1 Treatment of Packaging and non-hazardous waste
Packaging (non-returnable pallets, cardboard, fi lm, wooden packaging) and other non-hazardous waste
must be recovered by an approved service provider.
It is strictly forbidden to burn it or bury it or place it in any uncontrolled waste dump.
11.2 Treatment of professional WEEE
This product must not be disposed or processed with household waste; instead, it should be deposited at
an appropriate collection point for waste electrical and electronic equipment (WEEE).