13.6.4 Alarm for no mains power/restored mains power
The GSM chronothermostat can send a “No Mains Power” SMS message if there is a power
failure in the dwelling (blackout)� In addition, at the moment when the mains power is restored, the
chronothermostat can send a “Restored Mains Power” SMS message�
The “No Mains Power” SMS message is formed in this way:
No mains power!
+
Address Msg. (optional)
The “Restored Mains Power” SMS message is formed in this way:
Restored mains power!
+
Address (option)
For managing the two above-mentioned alarms, it is necessary to carry out the following configuration
procedures:
• Enabling the alarm for no mains power/restored mains power�
• Setting the warning times of the alarms for no mains power and/or restored mains power (optional)�
• Associating the alarm with the telephone numbers to which the SMS alarm message must be sent�
• Customizing the Address Msg� (optional)�
The configuration operations that, via SMS, can be performed on this alarm message are given in the
following points�
13.6.4.1 Enabling or disabling management of the alarm for no mains power/restored mains power
This option, if enabled, allows the chronothermostat to continuously check for mains power, sending
SMS messages to warn of any power failures (blackouts) and returns�
By default, the warning is made after No Mains Power or Restored Mains Power lasting 5 seconds,
indicated by the parameters TOFF and TON (please see the next paragraph 13�6�4�2)�
To enable it, send the following SMS message:
<user code>.AR.ON
Note:
No response SMS message is required from the chronothermostat 01913�
Example�
If the set user code is the default 1234 and you want to enable management of the alarm for no mains
power/restored mains power, send the following SMS:
1234.AR.ON