60
13.7.2 Two-position stable mode settings
The operation of the auxiliary output can be configured as two-position stable; this setting is described
in the following table:
COMMAND
STATUS
DESCRIPTION
ON
Auxiliary output on
The auxiliary output remains in the on state until the next OFF command
OFF
Auxiliary output off
The auxiliary output remains in the off state until the next ON command
To set the two-position stable mode, send the following SMS message:
<user code>.R1.BI
Note
: No response SMS message is required from the chronothermostat 01913�
Example�
If the set user code is the default 1234 and you want to configure the auxiliary output as two-position
stable, send the following SMS message:
1234.R1.BI
13.7.3 Setting the one-position stable mode and its activation time
The operation of the auxiliary output can be configured as one-position stable and it is possible to also
set the activation time correlated with this mode�
This setting is described in the following table:
COMMAND
STATUS
DESCRIPTION
ON
Auxiliary output on
The auxiliary output remains in the on state for a time equal to the set
activation time
OFF
Auxiliary output off
The auxiliary output remains in the off state until the next ON command
To set the one-position stable mode, send the following SMS message:
<user code>.R1.MONO.<activation time>
where
<activation time>
is the value of the activation time, expressed in seconds, that you
want to set; the possible values to set must be in the range between 0�1 s and 3600 s (60 minutes)�