70
The display (in the temperature field) shows the state of the input (OFF or on)�
13.10.4 Viewing and changing the input configuration parameters
This function is used to set and check the input configuration parameters (see paragraph 13�6�1 on
page 36); to view and edit these configuration parameters proceed as follows:
- enter the GSM menu;
- using button select the item
GSM COnF
and press
;
- using button select the item
In COnF
and press
;
The display (in the temperature field) shows the current enabling or disabling setting associated with
the input management (
dIS
=disabled or
Act
=enabled)�
With button
you can edit this setting while with
you return to the previous menu�
Pressing
confirms the setting made and you pass on to view the setting assigned for generating
the alarm event: ON CLOSED (
cLd
) or ON OPEN (
oPn
)�
With button you can change this setting; with
you confirm while with
you cancel the
change made�
On pressing
you pass on to view the setting of the activation time (
t On
)�
The display (in the temperature field) shows the numerical value of the activation time in seconds
(this value can be set between 0�1s and 10 min; default value 1s)�
With button
you can change this value; with
you confirm while with
you cancel the
change made�
Note
: Up to 10 s the increase is 0�1 s, after 10 s the increase is 1 s and after 60 s the increase is 1 min�
When setting times of less than one minute the display shows
t On SEC
while, for time values longer
than one minute, the abbreviation shown is
t On Min
�
On pressing
you pass on to view the setting of the activation time (
tOFF
)�
The display (in the temperature field) shows the numerical value of the deactivation time in seconds
(this value can be set between 0�1 s and 10 min; default value 1 s)�
With button
you can change this value; with
you confirm while with
you cancel the
change made�
Note
: Up to 10 s the increase is 0�1 s, after 10 s the increase is 1 s and after 60 s the increase is
1 min� When setting times of less than one minute the display shows
t OFF SEC
while, for time
values longer than one minute, the abbreviation shown is
t OFF Min
�