72
With button
you can change this value�
Note
: Up to 10 s the increase is 0�1 s, after 10 s the increase is 1 s and after 60 s the increase is
1 min� When setting times of less than one minute the display
shows
tMOn SEC
, while, for time
values longer than one minute, the abbreviation shown is
tMOn Min
�
With button
you confirm the setting made while with
you cancel the operation�
13.10.7 Enabling temperature alarms, viewing and setting the relevant thresholds and the
temperature differential for managing the temperature alarms
This function is used to enable or disable the temperature alarms (exceeding the threshold values,
etc�) and to set the parameters associated with them; to view and edit these parameters proceed as
follows:
- enter the GSM menu;
- using button select the item
GSM COnF
and press
;
- using button select the item
tEMP ALrt
and press
;
The display (in the temperature field) shows the current enabling or disabling setting of the temperature
alarm for exceeding the upper threshold Tsup� (
dIS
=disabled or
ACt
=enabled)�
With button you select the desired setting and you confirm with
�
On selecting
dIS
you pass directly to setting the activation of the temperature alarm for exceeding the
lower threshold (Tinf) otherwise you pass on to setting the temperature value of the upper threshold
(Tsup)�
Having done this the device displays the request for setting the temperature alarm for exceeding the
lower temperature threshold (Tinf)�
With button you select the desired state and you confirm with
�
If you set
dIS
you are returned to the main menu otherwise you pass on to setting the temperature
value of the lower threshold (Tinf)�
Subsequently you pass on to setting the temperature differential used for managing the temperature
alarms (DTA)�
The display (in the temperature field) shows the currently set value of the DTA�
With button it is possible to change this value; with button
you confirm the setting made while
with
you cancel the operation�