8.6.5 Thermal delta in nighttime reduction mode
The menu, via
and
, lets you set the difference between the remote reduction tem-
perature and Tcomfort temperature.
The remote reduction mode can only be activated via the multi-function input.
The hysteresis is a temperature increase/decrease that is applied to the Tcomfort temperature
when the multifunction input is activated). The value of the thermal delta is identical in both heating
and air conditioning with the only difference being that in the former case it determines a decrease
in the set point while in the latter case it determines an increase.
8.6.6 Antifreeze temperature
The menu, via
and
, lets you increase/decrease the value of the antifreeze temper-
ature
and .
Antifreeze mode is used to set a minimum temperature level to avoid damage to the pipework or
keep the room temperature from falling below a safety level.
8.7 Calibration setting
This menu lets you "calibrate" the temperature read by the timer-thermostat.
Using
and
, you can add or subtract (at intervals of 0.1°) a fixed amount from the temper-
ature detected by the timer-thermostat to make it equal, for example, to that of a sample thermometer.
CAUTION: For correct calibration it is recommended to wait until the timer-thermostat has been on
for at least 1 hour in a room at constant temperature.
Tap
to confirm your choice.
8.8 Multi-function input setting
This menu is used to set the operating mode of the multi-function input.
Via
and
you can select the following options:
•
: the state of the multi-function input is ignored by the device.
•
(Remote auto)
: the multi-function input (when enabled) activates the timer-thermostat in “Auto”
mode. In this situation the user cannot carry out any operations on the device other than consult the
main screen; with the multi-function input disabled, the default mode is "Antifreeze" (or OFF if on air-con-
ditioning) and the user can manage the timer-thermostat completely.
•
(remote reduction)
: the multi-function input (when enabled) forces a reduction in temperature
(which can be set via the submenu associated with that selection) with respect to “Tcomfort”.
In this situation the user cannot carry out any operations on the device other than consult the main screen;
with the multi-function input disabled, the timer-thermostat goes back into the previously set operating
mode and the user can manage the device completely.