Weather station, KNX standard, power supply 12-32 V DC or 12-24 V AC.

The weather station integrates with the By-me home automation system for managing 
temperature control, energy and automation systems. The weather station measures 
variables such as temperature, wind speed, rainfall and brightness whose values   can 
be used for:
- viewing on monitors;
- activating automation systems in the home automation system on exceeding the 

threshold based on limit values.

IMPORTANT: The weather station can also be installed before being configured 
as long as the physical address is assigned by pressing the configuration button.

CHARACTERISTICS.

• Auxiliary supply voltage AUX: 12-32 V  , 12-24 V~ SELV
• Absorption: 100 mA max, ripple 10%
• Current draw from the Bus: 10 mA
• Terminals: 

- Auxiliary power supply AUX
- TP bus connector

• Configuration push-button
• Configuration LED
• Configuration LED: 254 max
• Possible associations: 255 max
• Communication objects: 109
• Rain sensor heating: approximately 1.2 W 
• Temperature measurement range: -40°C - +80°C
• Definition (temperature): 0.1°C
• Accuracy (temperature): 

- 1°C with -10°C - +85°C
- 1.5°C with -25°C - +150°C

• Wind measurement range: 0 - 70 m/s
• Definition (wind): <10% of the reading
• Accuracy (wind): 25% with 0 - 15 m/s with an angle of incidence of 45° and mounting 

on a suitable support

• Brightness measurement range: 0 - 150,000 Lux
• Definition (brightness):    

- 1 Lux with 0-120 Lux
- 2 Lux with 121-1,046 Lux
- 63 Lux with 1,047-52,363 Lux
- 423 Lux with 52,364-150,000 Lux

• Accuracy (brightness): 35%
• Operating temperature: -30°C - +50°C (outdoor use)
• Protection class: IP44
• Dimensions: 96x77x118 mm (W x H x D) 
• Weight: approximately 170 g

OPERATION.

• 

Brightness measurement

: the current brightness is measured by the specific sensor. 

• 

Wind measurement

: the strength of the wind is measured electronically and is 

therefore quiet and reliable even in the event of hail, snow and sub-zero temperatures. 
The weather station is also able to detect whirlwinds and updraughts.

• 

Precipitation measurement

: the weather station is equipped with a sensor with a 

heated surface so that only the raindrops and snowflakes (and therefore not fog or 
dew) are measured as precipitation. Once it has stopped raining or snowing, the 
sensor dries quickly and the precipitation message is turned off.

• 

Temperature measurement

: the weather station measures the value of the current 

ambient temperature. 

• 

Control outputs for all values

: the limit values   can be set via the respective 

parameters or via the ETS communication objects.

• 

8 AND logic gates and 8 OR logic gates each one with 4 inputs

: the control 

operations themselves as well as the 8 logic inputs (in the form of communication 
objects) can be used as inputs for the AND and OR logic gates; the output of each 
gate can be configured as 1 bit or as 2 x 8 bits.

The weather station functions and parameters are configured via the ETS software; 
the program file (in VD format), the manual and the technical info sheet are 
available for download in the Software->Product Software section of the website 
www.vimar.com.

CONFIGURATION.

Take off the cover and press the configuration button to engage the device;

 

the bus 

address assigned by default is 

15.15.250

. Using ETS it is in any case possible to assign 

a different address to the weather station, overwriting the current value. 

When you press 

the button, do not touch any other components on the circuit board.

The weather station 01546 can also be used with the By-me home automation 
system by configuring it with EasyTool Professional. For the clone and updating 
the device the PC with the software must be connected on the same area-line 
as the weather station; the By-me router does not permit transferring KNX 
messages that are indispensable for the configuration. For all the details about the 
configuration procedures, see the EasyTool Professional installer manual.

INSTALLATION RULES.

• Installation should be carried out by qualified personnel in compliance with the current 

regulations regarding the installation of electrical equipment in the country where the 
products are installed.

• 

The installation, testing and commissioning of the weather station must be 
performed only by qualified personnel.

• The weather station should be installed in such a position as to allow optimal 

measurement of rainfall, wind, snowfall and sunshine by the sensors. 

• The weather station should not be located in parts of the building where there is any 

dripping onto the sensor especially when the precipitation is over.

• The weather station should not be located in areas of shade caused by the presence 

of trees, buildings or parts of them.

•  To enable measuring the wind correctly and, in the case of snowfall, prevent the 

weather station from getting covered with snow, it must be installed with a clearance 
beneath it of at least 60 cm. 

• Take care that no awnings create any shadows on the device and that it is not located 

downwind.

• The temperature measurement may be subject to alteration by external agents such 

as, for example, heating or cooling of the component on which the sensor is mounted 
(solar radiation, heating pipe or cold water pipe); to remedy this and achieve the 
required accuracy, use ETS to balance the temperature changes due to such sources 
of interference (temperature offset).

IMPORTANT:

• Do not open the device if there is a risk of ingress of water (rain); even a few drops can 

damage the circuit board. 

• Pay close attention to the connections; an incorrect connection may damage the 

sensor or the electronic device to which it is connected. 

• During installation, take care not to damage the temperature sensor (small plate at the 

back of the box).

• Do not detach or put strain on the cable connecting the circuit board and the 

precipitation sensor.

• After installing remove all the protection labels affixed for transportation. 
• 

After switching on the auxiliary voltage, the device will enter the initialization phase 
for a few seconds; during this time no data can be received from the bus.

• 

The measured wind strength, and therefore also the associated control outputs, 
may be used from 1 min after powering up with the supply voltage.

• At least twice a year check the state of cleanliness of the device and clean it if 

necessary; if there is too much dirt the sensor might not work properly.

• Do not use any high-pressure devices or blasts of steam for cleaning.
• 

During the cleaning process, in order to prevent any system components from 

moving and being a risk for people (for instance, movement of the window/awning 
if raining/windy), disconnect the device from the wall socket outlet (for example, 
disable/remove the fuse).

REGULATORY COMPLIANCE.

EMC directive.
Standards EN60730-1, EN 50491.

WEEE - Information for users

If the crossed-out bin symbol appears on the equipment or packaging, this means the product must 
not be included with other general waste at the end of its working life. The user must take the worn 
product to a sorted waste center, or return it to the retailer when purchasing a new one. Products for 
disposal can be consigned free of charge (without any new purchase obligation) to retailers with a 
sales area of at least 400 m

2

, if they measure less than 25 cm. An efficient sorted waste collection for 

the environmentally friendly disposal of the used device, or its subsequent recycling, helps avoid the 
potential negative effects on the environment and people’s health, and encourages the re-use and/
or recycling of the construction materials.

Summary of Contents for By-me 01546

Page 1: ...azione si veda il manuale installatore di EasyTool Professional REGOLE DI INSTALLAZIONE L installazione deve essere effettuata da personale qualificato con l osservanza delle disposizioni regolanti l installazione del materiale elettrico in vigore nel paese dove i prodotti sono installati L installazione le verifiche e la messa in funzione della stazione meteo possono essere effettuate solo da per...

Page 2: ... on the same area line as the weather station the By me router does not permit transferring KNX messages that are indispensable for the configuration For all the details about the configuration procedures see the EasyTool Professional installer manual INSTALLATION RULES Installation should be carried out by qualified personnel in compliance with the current regulations regarding the installation o...

Page 3: ...e aire ligne que la station météo le routeur By me ne permet pas le passage de messages KNX indispensables pour la configuration Pour tous les détails relatifs aux procédures de configuration consulter le manuel de l installateur d EasyTool Professional CONSIGNES D INSTALLATION L installation doit être confiée à des personnel qualifiés et exécutée conformément aux dispositions qui régissent l inst...

Page 4: ...anded cable 4 Connector for connecting the cable of the precipitation sensor under the front cover of the weather station 5 Space for feeding through the power supply cable and the bus cable 6 KNX TP bus connector We recommend using the KNX cable art 01890 using a corrugated pipe for the outside or to protect the cable from UV radiation 7 Configuration button 8 Configuration LED 1 Capteur de détec...

Page 5: ... support perpendiculaire à la paroi ou au mât 3 1 Montaggio a parete installare la parte piana verso la parete e la staffa a mezzaluna verso l alto Wall mounting install the flat part towards the wall and the half moon bracket upwards Montage mural installer la partie droite vers le mur et l étrier en demi lune vers le haut Staffa Bracket Étrier 3 2 Montaggio su sostegno installare la parte arcuat...

Page 6: ...one devono innestarsi nelle guide del la scatola Per togliere il sensore dal supporto tirarlo verso l alto ed estrarlo opponendosi all arresto a scatto Move the box to the top of the installed mounting frame the coupling teeth should engage in the box guides To remove the sensor from the mounting frame pull it upwards and take it out against the resistance of the fastener Déplacer la boîte dans la...

Reviews: