- 1 -

CAUTION:  
DO NOT SWITCH ON THE COMPRESSOR IF THE CONDENSING UNIT IS 
EQUIPPED WITH A LOW AMBIENT CONDITION KIT UNTIL THE UNIT HAS 
BEEN PLUGGED IN FOR 24 HOURS. 

 

2.  Valve Operation (Condensing unit) 

 

   

        BACK POSITION                    FRONT POSITION                        MIDDLE POSITION 

Fig. 1 ROTALOCK Valve Operation

 

 
 

 

         BACK POSITION                          FRONT POSITION                     MIDDLE POSITION 

Fig. 2 Base Valve Operation

 

 

1 - Process & Manometer; 2 - Receiver/Compressor Suction  
3 - Liquid/Suction Line; 4 - Pressure Control 

 

Back Position

: Process and manometer port closed for normal operation

 

Front Position

: Connection to liquid or suction line closed 

Middle Position

: All ports open for evacuation, charge and manometer reading 

 

3. Evaporator Unit 
 

  The WM15-25SFCW evaporator units shall be installed for wall mount with 

the air supply on the top and air return on the bottom. 

  Supply and return air flow from the evaporator unit shall be unobstructed 

for at least 1 foot. 

Summary of Contents for WINE-MATE 250SCU

Page 1: ...a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two units After the units and the lines are installed th...

Page 2: ...ion 1 Process Manometer 2 Receiver Compressor Suction 3 Liquid Suction Line 4 Pressure Control Back Position Process and manometer port closed for normal operation Front Position Connection to liquid...

Page 3: ...evaporator unit including liquid line connection solenoid valve expansion valve and suction line connection returning to insulated suction line suction valve and then condensing unit Use inverted siph...

Page 4: ...CONNECTION SIZES OF CONDENSING UNIT AND THE LINE CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY THE SAME AS THE ABOVE SPECIFIED LINE SIZES IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORAT...

Page 5: ...pressure High superheat and high subcooling o low to normal suction pressure and high head pressure High to normal superheat and high subcooling g Undercharge h Liquid line restricted after receiver...

Page 6: ...n 170 psig Cut out 120 psig Differential 50 psig It may need to adjust the setting in the field to prevent short fan cycle 10 Use of the crankcase heater if applicable for low ambient kit The crankcas...

Page 7: ...led components d Liquid refrigerant in the compressor e Low pressure switch shutting down the system a Check for proper voltage b Check all wirings and connections c Check start relay start capacitor...

Reviews: