- 9 -
7. How to calibrate the air probe
If the actual cellar temperature differs from the setting temperature, set
parameter
ot
= actual cellar temperature minus set-point.
8. How to adjust defrost settings
I
n case there is excessive frost, the parameters
FnC
=
C-y
, idF
=
4
and
MdF
=
20
can be used to avoid frost.
9. How to adjust the humidity
The parameter
Fon
is used to adjust the humidity in the wine cellar. Higher
Fon
results in higher relative humidity.
Use a separate hygrometer to monitor the
humidity.
10. How to set alarm call
1) S
peech notice will be sent to your phones when the cellar temperature is
ALU
higher or
ALL
lower than the set-point
Set
.
2) In order to test the call function, set parameters
Ald
= 0 and
dAO
= 0. After
testing, set
Ald
= 60 and
dAO
= 23.
11. How to set cellar heater
The heater turns on at
SAA
minus
Shy
;
the heater turns off at
SAA
.
NOTE
Use a forced air heater to warm up the wine cellar.
If there is a thermostat on the heater, bypass it or set the
thermostat at the highest level.
If the heater runs more than 10 A current, use a 120VAC coil
contactor.