background image

                                                       

 

                       

 

- 14 -

Installer’s Instruction 

Federal law requires that WINE-MATE split cooling systems be 

installed by an EPA certified refrigeration technician

 

1. General Instructions 

 
WINE-MATE split system is shipped as components and is ready for use only 
after a certified refrigeration technician has properly installed the system. Proper 
installation is critical. Vinotemp can only warrant the quality of the components. 
The installation and proper operation of the system must be warranted by the 
installer. Installation of the system must be done in accordance with all state and 
local building and electrical codes.  
The condensing unit and evaporator unit are connected by a liquid line and an 
insulated suction line that are supplied by the installer. These lines must be 
properly sized for the distance between the two units. After the units and lines 
are connected, the system must be checked for restriction, pressurization and 
leak. Then the system must be evacuate and charged with refrigerant. 
Refrigerant amount will vary depending on the length of line set. 
 

Parts included: 
 

Evaporator Unit (liquid line solenoid valve and expansion valve installed) 
Condensing Unit (pressure control, water regulation valve, discharge and suction 
valves and installed) 
Liquid Filter 
Liquid Indicator 
Temperature Controller (4.5”LX4.5”WX3.75”D) + Air Probe 
 

Parts not included: 
 

Liquid line copper tubing 
Suction line copper tubing 
Insulated ducts 
Water lines 

Summary of Contents for Wine-Mate WM-2500SSHWC

Page 1: ...uct Split Cooling System Installation Operation Care Manual WM 2500SSHWC WM 4500SSHWC WM 6500SSHWC WM 8500SSHWC w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he...

Page 2: ...1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 20 AMP circuit for WM 2500SSHWC and 30 AMP for WM 4500 8500SSHWC are required...

Page 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 24 Customer Support 26 Warran...

Page 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Page 5: ...se and compressor vibration are isolated SSHWC condensing units are water cooled so that exhaust ventilation is not needed SSHWC evaporator units are designed to provide chilled air to wine a cellar t...

Page 6: ...x18 2500 220 250 R134a 115V 60HZ 0 8A 115V 60HZ 5 7A 35 40 WM 4500SSHWC WM 45SFCH 25 125x22 875 x16 375 18 WM 450SCU WC 24x18x18 4500 380 1000 R134a 115V 60HZ 1 8A 115V 60HZ 6 9A 45 60 WM 6500SSHWC WM...

Page 7: ...o lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock t...

Page 8: ...etting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setti...

Page 9: ...lar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temper...

Page 10: ...elay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative...

Page 11: ...aning To clear any sediment that may accumulate the water regulating valve may be manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush 2 Condensate...

Page 12: ...temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it...

Page 13: ...a Check compressor windings start relay and overload protector b Check water flow c Call service for removing refrigerant d Call service for information 9 Evaporator fan running too long a Post compre...

Page 14: ...ture setting 14 Circuit tripping a Incorrect fuse or breaker b Incorrect wirings c Failed components a Check for proper fuse or breaker b Check for wirings and connections c Call service 15 Noisy oper...

Page 15: ...ndensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two un...

Page 16: ...15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 25 85SFCH Evaporator Unit...

Page 17: ...16 Fig 4 WM 250 850SCU WC Condensing Unit Fig 5 Liquid Filter Fig 6 Liquid Indicator...

Page 18: ...p must be used 3 Condensing Unit Installation 1 Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun The location shall be adequately ventilated and shall not be sub...

Page 19: ...WM 4500SSHWC WM 450SCU WC 0 4 3 8 FPT 1 2 ODF SOLDER 0 2 WM 6500SSHWC WM 650SCU WC 0 6 3 8 FPT 1 2 ODF SOLDER 0 2 WM 8500SSHWC WM 850SCU WC 0 8 3 8 FPT 1 2 ODF SOLDER 0 4 4 Temperature Controller and...

Page 20: ...on sizes of evaporator unit are not necessary the same as the listed refrigeration line sizes If the condensing unit is installed above the evaporator unit use the suction line one listed size smaller...

Page 21: ...all electrical components using the wiring diagrams in accordance with all state and local codes 8 Evacuating Charging and Starting the system CAUTION Always use the superheat and subcooling pressure...

Page 22: ...an Speed Control 3 The subcooling at the condensing unit shall be around 10 F The charge may be complete when there are no more bubbles forming in the liquid indicator 4 Head pressure is maintained co...

Page 23: ...eat and zero subcooling k High suction pressure and low head pressure Low superheat and low subcooling l High suction pressure and high head pressure Low superheat and high subcooling m High to normal...

Page 24: ...high subcooling evaporator iced t Evaporator restricted u Expansion valve restricted v Both evaporator and condenser restricted liquid and suction lines connected wrong w Liquid line restricted befor...

Page 25: ...rical Wiring Diagrams CAUTION Hidden lines are the field wirings Use minimum 14 gauge wires for power lines A safety switch is always recommended for the condensing unit Fig 14 WM 2500 4500SSHWC Wirin...

Page 26: ...25 Fig 15 WM 6500 8500SSHWC Electrical Wiring Diagram...

Page 27: ...6 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Page 28: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Page 29: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Reviews: