Cellar Construction Guide 

 
This is only a guide and shall be considered as the minimum requirements. 
 
All interior walls, ceilings and floors shall have a vapor barrier and a minimum of 
R13  insulation.  All  exterior  walls  and  ceiling  shall  have  a  vapor  barrier  and  a 
minimum of R19 insulation. The vapor barrier shall be installed on the warm side 
of insulation. All joints, door frames, electrical outlets or switches and any pipes 
or  vents  that  go  through  the  cellar  shall  be  sealed  to  prevent  air  and  moisture 
leaking  into  the  cellar.  Concrete,  rock,  and  brick  are  not  insulations  or  vapor 
barriers. Doors shall be of a minimum size, insulated to at least R13 and tightly 
sealed with high quality weather stripping. Be sure to seal the bottom of the door 
and fill gap between the door’s frame and wall before installing the cap molding.  
 
In  order  to  maintain  55  °F  in  the  wine  cellar,  the  ambient  temperature 
surrounding  the  cellar  shall  not  exceed  the  temperature  of  the  cellar  by  more 
than 25 °F. No cellar walls shall receive direct sun or strong wind.  
 
Lighting shall be of low wattage, with a timer to insure lights are not left on when 
the cellar is not occupied.  
 
The  cooling  system  will  not  be  able  to  maintain  the  proper  temperature  if  fresh 
moisture-laden air is constantly being introduced to the cellar. Symptoms of this 
condition  are;  cooling  unit  runs  all  the  time  with  only  a  slight  reduction  in 
temperature  and/or  water  overflows  from  the  cooling  unit.  Because  of  the 
temperature  difference  between  the  inside  and  outside,  very  small  cracks  can 
allow large amounts of outside air to enter into the cellar. Please be aware that 
moisture  can  pass  through  solid  concrete,  paint  and  wood.  Often  a  newly 
constructed  cellar  contains  fresh  wood,  paint,  concrete  and  other  building 
materials. These materials contain large amounts of moisture. When placed into 
operation in this type of environment, the system will work harder to remove this 
extra moisture resulting in increased “run” time. 

 
 
 
 
 
 
 
 
 
 

 
 
 
 

Summary of Contents for WINE-MATE WM-2500SSO

Page 1: ...LA WM 4500SSO WM 4500SSO LA w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns s Vinotemp International Corp 732 South...

Page 2: ...1 Important Safety Information...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Warranty 27...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...m storage of wine like that in natural caves SSO evaporator units can be installed through the ceiling outside a wine cabinet or room The evaporator units are designed to maximize storage space SSO co...

Page 6: ...with R13 interior and R19 exterior insulations Higher ambient temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Page 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Page 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Page 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Page 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Page 16: ...Unit L x W x H Electrical Rating Evap Unit Cond Unit Min Circuit Ampacity A Weight lb Evap Unit Cond Unit WM 2500SSO WM 25SFCO 48 x 12 x 8 1 8 45 x 9 1 8 WM 250SCUR 18 x 14 x 12 115V 60HZ 1A 115V 60HZ...

Page 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 45SFCO Evaporator Unit...

Page 18: ...the floor or the air return area but it shall not be located in the air supply area or other areas where air is not circulated 3 Air probe can be pulled out of the temperature controller up to 5 ft If...

Page 19: ...e flooding and shaded from direct sun It shall not be exposed to temperatures higher than 110 F or lower than 50 F 3 Leave minimum 5 ft clearance for the air exhaust side and leave minimum 1 foot clea...

Page 20: ...om flooding back to the compressor If the elevation difference is more than 10 ft use both inverted U trap and suction accumulator 4 If the condensing unit is located more than 10 ft above the evapora...

Page 21: ...e compressor after the condensing unit has been powered for 12 hours 1 Turn both discharge and suction valves in the middle positions 2 Connect the manifold high or low pressure hose to the discharge...

Page 22: ...ressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It is necessary to adjust the setting in the field to rea...

Page 23: ...liquid indicator 3 The head pressure shall be 120 150 psig at 70 90 F condensing unit operating temperatures 4 The evaporator s constant pressure expansion valve is set around 30 35 psig 35 40 F at f...

Page 24: ...2 High suction pressure and low head pressure Low superheat and low subcooling 3 High suction pressure and high head pressure Low superheat and high subcooling 4 High to normal suction pressure and hi...

Page 25: ...e and high head pressure Normal to high superheat and high subcooling 8 Liquid line restricted after receiver solenoid valve restricted 9 Suction line restricted 10 Air restricted at evaporator evapor...

Page 26: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Page 27: ...26 Fig 15 WM 2500 4500SSO LA Electrical Wiring Diagram...