- 15 -
Fig. 5 Temperature Controller (4.25”L x 3.75”D x 4.25”H)
Parts included:
Packaged Cooling system
Temperature Controller (4.5”L x 4.5”W x 3.75”D) & Air Probe
Parts not included:
Insulated ducts
CAUTION
If the unit operates below 50°F, a low ambient condition kit
will be required.
2. Location
•
Place the cooling unit in a properly ventilated location. If it is not, heat
exhausted by the unit will build up and the cooling unit will not operate
properly.
•
The cooling unit shall be elevated to avoid possible flooding and shaded from
direct sun. It shall not be exposed to temperatures higher than 110 °F or
lower than 50 °F.
•
Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot
clearance for fresh air intake.
•
Cold air supply shall be unobstructed for minimum 12” for a direct blow
installation or 2” for a deflector installation. Cellar air return shall be
unobstructed for minimum 6”.
3. Mounting
•
The unit must be mounted on a floor or slab that is level and strong enough to
support up to 300lb.
•
There are six ½” bolts required to secure the unit base.