User’s Manual
Arctic IEC-104 Gateway
43
Viola Systems Ltd.
Use packet collector
Use packet collector
Type Boolean
Units N/A
Value range
No, Yes
Note
Max bytes
Defines the maximum bytes trigger for packet collector. Before a new packet is inserted intto
the packet collector buffer the amount of bytes is checked. If the insertion of the new packet
would cause the number of bytes in the packet collector to exceed MAX BYTES the old
content is sent to the network before inserting the new one.
Maximum collected bytes
Type Packet
size
Units Bytes
Value range
1-1500
Note
The value should be smaller than the MTU/MRU of network
used.
Max time
Defines the maximum collect time trigger for packet collector in 0.1 secs
increments
for packet
collector. If there has been data on packet collector over MAX TIME the data is sent to network.
Maximum collected time
Type Timeout
Units 0.1
seconds
Value range
1-255
Note
The value must be smaller than
t1
.