background image

Manual VIPA System HMI 

Safety information

 

HB160E - TP - RE_605-3B1F0 - Rev. 10/16 

 

Safety information 

 

The Touch Panels are constructed and manufactured for: 

• 

VIPA CPUs 11x, 21x, 31x, 51x and S7-300/400 from Siemens 

• 

communication and process control 

• 

general control and automation applications 

• 

industrial applications 

• 

operation within the environmental conditions specified in the technical 
data 

• 

installation into a cubicle 

 

Danger! 

This device is not certified for applications in 

• 

in explosive environments (EX-zone) 

 

The manual must be available to all personnel in the 

• 

project design department 

• 

installation department 

• 

commissioning 

• 

operation 

 

The following conditions must be met before using or commissioning 
the components described in this manual:

 

 

• 

Modification to the process control system should only be carried out 
when the system has been disconnected from power! 

 

• 

Installation and modifications only by properly trained personnel 

 

• 

The national rules and regulations of the respective country must be 
satisfied (installation, safety, EMC ...) 

 

National rules and regulations apply to the disposal of the unit! 

 

Applications 
conforming with 
specifications 

 

Documentation 

 

Disposal 

Summary of Contents for 605-3B1F0

Page 1: ...VIPA HMI Touch Panel 605 3B1F0 Manual HB160E_TP RE_605 3B1F0 Rev 10 16 April 2010...

Page 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...

Page 3: ...ssioning 2 4 Connection to a PLC system 2 11 Operating system Windows CE 2 12 Communication via ActiveSync 2 17 Integrated Server 2 20 Access to the network resources 2 27 Integration to WLAN network...

Page 4: ...Contents Manual VIPA System HMI ii HB160E TP RE_605 3B1F0 Rev 10 16...

Page 5: ...so find the dimensions that are required for the installation The chapter closes with the technical data Chapter 2 Deployment Touch Panel This chapter deals with the employment of the Touch Panel At t...

Page 6: ...s for every chapter An index at the end of the manual The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Button Buttons are put in brackets e g NEXT o...

Page 7: ...ve environments EX zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using...

Page 8: ...Safety information Manual VIPA System HMI 4 HB160E TP RE_605 3B1F0 Rev 10 16...

Page 9: ...TP 605CQ CAN from VIPA Besides of a description of the single components of the Touch Panel you will also find the dimensions that are required for the installation The chapter closes with the technic...

Page 10: ...reby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical lo...

Page 11: ...itable for monitoring and controlling of process cycles Microsoft Windows CE V 5 0 full version as option Different HMI SCADA Runtime selectable Work memory 64Mbyte about 6Mbyte memory for user data o...

Page 12: ...1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply T o u c h P a n e l 1 2 3 3 Display with touch sensitive area touch screen 1 Compact Flash 2 MMC SD 1 2 Note Please reg...

Page 13: ...5 6 7 8 1 RS422 485 interface COM 2 2 RS232 interface COM 1 3 CAN interface 4 Host USB A interface 5 Slave USB B interface 6 RJ45 jack for Ethernet communication 7 Slot for DC 24V voltage supply 8 Slo...

Page 14: ...vice Slot for CF Here you may plug a CompactFlash type II The card may be plugged and removed during runtime and is immediately listed as Storage Card at My Device Every CompactFlash storage module ha...

Page 15: ...V 7 n c 8 TxD Line B 5 4 3 2 1 9 8 7 6 9 RxD Line B TxD A TxD B RxD A RxD B Shield RS422 Periphery 3 8 4 9 M5V TxD TxD RxD RxD P5V 5 6 Serial bus connection in 2 wire technology using half duplex mode...

Page 16: ...er rate up to 115 2kBaud Connection RS232 9pin plug Connection RS232 Pin RS232 1 CD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 1 2 3 4 5 6 7 8 9 9 RI RxD TxD GND TxD RxD 3 2 GND 5 RTS CTS 7 8 Shield RS...

Page 17: ...nt is as follows Slave USB B Pin Assignment 1 VCC 2 DM 3 DP 2 1 3 4 4 GND The USB A interface of your PC can be connected to the Slave USB B interface of your Touch Panel deploying the USB programming...

Page 18: ...W x H 200 x 144mm Front panel W x H 212 x 156mm Display size W x H 115 2 x 86 4mm Back side W x H x D 198 x 142 x 37mm Installation depth 37mm Note The degrees of protection are only guaranteed when...

Page 19: ...mperature 0 50 C Relative humidity max 85 Storing Transport temperature 20 to 60 C Display Size 5 7 115 2 x 86 4mm Resolution 240 x 320 320 x 240 Colors TFT color 64K colors MTBF Backlights 25 C ca 70...

Page 20: ...Chapter 1 Hardware description Manual VIPA HMI 1 12 HB160E TP RE_605 3B1F0 Rev 10 16...

Page 21: ...onnection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Topic Page Chapter 2 Deployment Touch Panel 2 1 Install...

Page 22: ...le For the installation into a operating tableau and control cabinet fronts the Touch Panel requires the following front plate cutting W H Touch Panel W x H in mm 605 3B1F0 200 x 144 The fixing techni...

Page 23: ...e flexible wires without end case as well as stiff wires You fix the conductors to the CageClamps like this DC 24V 1 2 3 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm...

Page 24: ...bles are permitted Signal cables must not be let within the same cable shaft as high voltage cables As soon as the Touch Panel is provided by power supply the Touch Panel starts with user area of the...

Page 25: ...of Permanent Registry With Backup the files of the flash disk and the Registry settings may be stored The backed up files may be restored by Restore With this button you may return to the user area W...

Page 26: ...t Settings are activated With disabling Run on Startup the Touch Panel starts with the Windows operating system The functions preset at Settings are ignored With enabling Enable User Interface the Tou...

Page 27: ...n the user respectively administrator area Here new buttons may be configured and assigned with corresponding programs You may choose Normal for the user area or Advanced for the administrator area Wi...

Page 28: ...sword is defined you were prompted to enter the password If there is no password defined the administrator area is opened On delivery there is no password preset If you have forgot you password by ena...

Page 29: ...re programs may be added which have to start in the background during startup e g VNC server or transport services With enabling the checkbox Autostart the program is always executed on startup after...

Page 30: ...on the Touch Panel start via the button Control Panel the tool Com2 Configuration In the opened dialog window you activate the RS485 or the RS422 interface Default RS485 To remain the settings permane...

Page 31: ...ed runtime version of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via field...

Page 32: ...ed to the absolute essentials with mouse operation touch screen that requires only small hardware resources Here the 2 icons My Device and Recycle Bin may exclusively be found at the Desktop The Profe...

Page 33: ...selects the touched objects Characteristics with Windows CE Professional Plus V 5 0 In the Professional Plus version mouse functions are fully supported As soon as the touch screen is touched with th...

Page 34: ...tings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for minimizing The switch between the applications happens via this but...

Page 35: ...clusively entered via the software keyboard Keyboard Normal At pushed SHIFT key Meaning Home Position 1 End End BS Backspace up dn lt rt pgup Page pgdn Page ins Insert del Delete Tab Tabulator Shift C...

Page 36: ...ou may use the grid pattern to preset a double click velocity and test this on the symbol below OK takes over the set value The calibration of the touch screens happens via the register Calibration by...

Page 37: ...Panel from the PC via ActiveSync you have to install it at the PC ActiveSync is freeware and may be downloaded from www microsoft de Download the ActiveSync from the Microsoft website and start the fi...

Page 38: ...ouch Panel is recognized and the dialog window new partnership opens Choose yes that you want to fix a partnership and push Next In the now opening window de activate all synchronization settings and...

Page 39: ...able the Touch Panel to be accessed via Ethernet you have to activate the option enable network connection in ActiveSync via File Connection Settings Disconnect the USB cable of the Touch Panel Confir...

Page 40: ...via START Programs KuK Tools before switching off Per default the following server are integrated ftp server activated http server activated Telnet activated VNC not activated Phrases that are used in...

Page 41: ...ns for an ftp connection If there are still problems with the ftp access ask your system administrator ftp access possible with version 5 5 or higher use passive ftp mode activate directory view for f...

Page 42: ...nnect your Touch Panel with the network where your PC is a member via an Ethernet cable Switch on your Touch Panel As soon as your Touch Panel is connected via Ethernet you may monitor the IP address...

Page 43: ...into the address bar IP address webadmin Enter the following into the authentification User name wince Password vipatp Remember to store your changes permanently in the registry via Start Programs KuK...

Page 44: ...plication is not possible The establishing of a Telnet connection is password protected and has the following approach Start a Telnet client like for example MS DOS console at your PC and enter the fo...

Page 45: ...Rev 10 16 2 25 After establishment of a Telnet connection the Touch Panel provides you with commands A list of possible commands with a short description is available via the command help By beginnin...

Page 46: ...n the VNC server is on delivery deactivated The VNC connection establishment has the following approach Click on and open the Windows directory You have to deactivate every option at View Options to s...

Page 47: ...test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection of a local name at the Touch Panel with a...

Page 48: ...etwork printer For example you may print the content of the current directory with dir network printer The listing of all network connections of your Touch Panel happens via net use You may terminate...

Page 49: ...s is opened Continue with WLAN integration Please regard only WLAN USB sticks are supported with the chip of the company Funkwerk inside PowerOFF the Touch Panel Plug the WLAN USB stick to the USB A i...

Page 50: ...tivated For this open the register Wireless Information in the dialog window and click to the Advanced button The following window is shown By activating of Automatically connect to non preferred netw...

Page 51: ...sed Switch off the power supply from your panel Plug the memory card to your panel and switch on the power supply again As soon as a new firmware is found at the memory card it is downloaded to the To...

Page 52: ...Chapter 2 Deployment Touch Panel Manual VIPA HMI 2 32 HB160E TP RE_605 3B1F0 Rev 10 16...

Page 53: ...Here we describe possible paths in which interference can enter the controller how you ensure the electromagnetic compatibility EMC and how to approach shielding and screening issues Topic Page Chapte...

Page 54: ...industrial environments and complies with EMC requirements to a large degree In spite of this you should implement an EMC strategy before installing any components which should include any possible s...

Page 55: ...te to the time wise change of the voltage Interference through parallel signal lines Static discharge of the personnel Contactors Inductive coupling Automation System Disruptor inductive coupling line...

Page 56: ...groups High voltage lines power supply lines signal lines data lines Always install high voltage lines and signal or data lines in separate channels or bundles Install signal and data lines as close...

Page 57: ...cent lamps Create a single reference potential and ensure that all electrical equipment is grounded wherever possible Ensure that grounding measures are implemented effectively The controllers are ear...

Page 58: ...may only get voltage in case of an error The ground must not adopt dangerous contact voltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid gr...

Page 59: ...to divide the cables in different groups and install each group itself Group A screened bus and data lines screened analog lines unshielded lines for direct voltage 60V unshielded lines for alternatin...

Page 60: ...be installed on metallic cable trays A galvanic connection must be provided for joints between cable trays You must abide by the applicable lightning protection and grounding regulations when install...

Page 61: ...mm 2 Cu for equipotential bonding conductors up to 200m 25mm2 Cu for equipotential bonding conductors exceeding 200m Use copper or galvanized steel for equipotential bonding conductors These must be c...

Page 62: ...recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to the screening neutral rail Note Potential differences can give rise to an equ...

Page 63: ...ections of DC activated inductors Connections of AC activated inductors using a diode using a Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU Th...

Page 64: ...l contact washer Have the connection been protected from corrosion e g by means of grease Have doors been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabli...

Page 65: ...ion 1 8 F Firmware update 2 31 Flash disc 1 6 ftp server 2 21 H http server 2 23 I Installation 2 2 cutting 2 2 guidelines 3 1 L Login data 2 20 M Memory management 1 6 MMC 1 6 N net use 2 27 net view...

Page 66: ...Index Manual VIPA System HMI A 2 HB160E TP RE_605 3B1F0 Rev 10 16 M Stich...

Reviews: