Safety information

 

Manual VIPA HMI 

 

HB160E - TP - RE_62M-JEE0 - Rev. 11/14 

 
 

 

Summary of Contents for 62M-JEE0

Page 1: ...VIPA HMI Touch Panel 62M JEE0 Manual HB160E_TP RE_62M JEE0 Rev 11 14 April 2011 ...

Page 2: ...ic Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declaration of Conformity DoC please contact your local VIPA customer service organization Trademarks VIPA SLIO System 100V System 200V System 300V System 300S System 400V System 500S and Commander Compact ...

Page 3: ...tallation 2 2 Commissioning 2 4 Connection to a PLC system 2 12 Operating system Windows Embedded CE 6 0 2 13 Communication via ActiveSync 2 19 Integrated Server 2 21 Access to the network resources 2 28 Firmware update 2 30 Chapter 3 Installation Guidelines 3 1 Basic rules for the EMC equitable assembly of installations 3 2 EMC equitable assembly 3 6 EMC equitable cabling 3 7 Special precautions ...

Page 4: ...Contents Manual VIPA HMI ii HB160E TP RE_62M JEE0 Rev 11 14 ...

Page 5: ...or the installation The chapter closes with the technical data Chapter 2 Deployment Touch Panel This chapter deals with the application of the Touch Panel At the beginning of the chapter you get information about the assembly and the connection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Chapter 3 Installati...

Page 6: ... the topics for every chapter The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Button Buttons are put in brackets e g NEXT or OK Key Key entry are put in brackets e g STRG A Display output Display outputs are illustrated as Courier e g flashdisk Keyboard entry Keyboard entries are illustrated as Courier bold e g flashdisk Dir Terms Menus Display ...

Page 7: ...environments EX zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning the components described in this manual Modification to the process control system should only be carried out when the system has been disconnected from power Installation and modificat...

Page 8: ...Safety information Manual VIPA HMI 4 HB160E TP RE_62M JEE0 Rev 11 14 ...

Page 9: ...el TP 612C from VIPA Besides of a description of the single components of the Touch Panel you will also find the dimensions that are required for the installation The chapter closes with the technical data Topic Page Chapter 1 Hardware description 1 1 Safety information for Users 1 2 Properties 1 3 Structure 1 4 Components 1 6 Dimensions 1 10 Technical Data 1 11 Overview Content ...

Page 10: ...reby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices and meticulous attention to the applicable rules and regulations for handling the respective equipment can prevent failures of electrostatic...

Page 11: ...onitoring and controlling of process cycles Windows Embedded CE 6 0 Different HMI SCADA Runtime selectable 800MHz pulse frequency Work memory 128Mbyte about 1800Mbyte memory for user data on board CF Card II and MMC SD card slot Horizontal and vertical display selectable in 90 steps RS232 RS422 485 MPI PROFIBUS DP slave Ethernet USB A and USB B interfaces on board Robust aluminium die casting case...

Page 12: ...cture 1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply T o u c h P a n e l 1 2 3 3 Display with touch sensitive area touch screen 1 Compact Flash 2 MMC SD 1 2 Note Please only use storage media which are tested and approved by VIPA GmbH Front view Side view ...

Page 13: ...OM 1 3 MPI PROFIBUS DP RS485 interface 4 2x Host USB A interface 5 Slave USB B interface 6 7 RJ45 jack for Ethernet Communication switch 8 Slot for DC 24V voltage supply 9 Slot for CF SD MMC storage medium Note Please regard that the Touch Panel always has to be supplied with external voltage Bottom view Interfaces TP 612C 12 1 62M JEE0 Components ...

Page 14: ...k at My Device Slot for CF Here you may plug a CompactFlash type II The card may be plugged and removed during runtime and is immediately listed as Storage Card at My Device Every CompactFlash storage module has a pulling edge Hold the CompactFlash in the way that the pulling edge points to the left side Push the storage module without much power into the slot until the impact To remove the card t...

Page 15: ...c 8 TxD Line B 5 4 3 2 1 9 8 7 6 9 RxD Line B TxD A TxD B RxD A RxD B Shield RS422 Periphery 3 8 4 9 M5V TxD TxD RxD RxD P5V 5 6 Serial bus connection in 2 wire technology using half duplex mode Connection RS485 isolated TxD A TxD B RxD A RxD B Shield RS485 Periphery 3 8 4 9 M5V RxD TxD RxD TxD P5V 5 6 Periphery RxD TxD RxD TxD PROFIBUS DP MPI interface Connection RS485 9pin jack Connection RS485 ...

Page 16: ...er rate up to 115 2kBaud Connection RS232 9pin plug Connection RS232 Pin RS232 1 CD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 1 2 3 4 5 6 7 8 9 9 RI RxD TxD GND TxD RxD 3 2 GND 5 RTS CTS 7 8 Shield RS232 Periphery Shield An RJ45 jack provides the interface to the twisted pair cable required for Ethernet The pin assignment of this jack is as follows 8pin RJ45 jack Pin Signal 1 Transmit 2 Transmit 3...

Page 17: ...nt is as follows Slave USB B Pin Assignment 1 VCC 2 DM 3 DP 2 1 3 4 4 GND The USB A interface of your PC can be connected to the Slave USB B interface of your Touch Panel deploying the USB programming cable The USB programming cable is delivered by VIPA with order No VIPA 670 0KB10 The Touch Panel has got an integrated power supply The power supply has to be provided with DC 24V 20 4 28 8V For thi...

Page 18: ...tion cutting W x H 311 x 249 Front panel W x H 325 x 263 Back side W x H x D 309 x 247 x 45 Installation depth 45 Dimensions in mm Note The degrees of protection are only guaranteed when the following is observed Material thickness at the mounting cut out 1 5 6mm The deviation from the plane for the panel cut out is 0 5mm This condition must be fulfilled for the mounted HMI device Permissible surf...

Page 19: ...esistive Keyboard external via USB Mouse external via USB Interfaces MPI PROFIBUS DP RS485 isolated MPI PROFIBUS DP connector Sub D 9 pin female CAN CAN connector Serial COM1 RS232 COM1 connector Sub D 9 pin male Serial COM2 RS422 485 isolated COM2 connector Sub D 9 pin female Number of USB A interfaces 2 USB A connector USB A host Number of USB B interfaces 1 USB B connector USB B device Number o...

Page 20: ...side IP 65 Protect type back side IP 20 Dimensions Front panel 325 x 263 x 7 5 mm Rear panel 309 x 247 x 45 mm Installation cut out Width 311 mm Height 249 mm Minimum 1 5 mm Maximum front panel thickness 6 mm Weight 3674 g Environmental conditions Operating temperature 0 C to 50 C Storage temperature 20 C to 60 C Certifications UL508 certification in preparation ...

Page 21: ...y and the connection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Topic Page Chapter 2 Deployment Touch Panel 2 1 Installation 2 2 Commissioning 2 4 Connection to a PLC system 2 12 Operating system Windows Embedded CE 6 0 2 13 Communication via ActiveSync 2 19 Integrated Server 2 21 Access to the network reso...

Page 22: ...ble For the installation into a operating tableau and control cabinet fronts the Touch Panel requires the following front plate cutting W H Touch Panel W x H in mm 62M JEE0 311 x 249 The fixing technique is integrated in the casing of the Touch Panel and accessible via the backside For the installation a small slit screwdriver is required Push the operator panel 3 from the front side into the fron...

Page 23: ...use flexible wires without end case as well as stiff wires Fix the conductors to the CageClamps like this DC 24V 1 2 3 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm test tip 1 2 3 The picture on the left side shows the cabling step by step from top view For cabling you push the locking vertical to the inside with a suiting screwdriver and hold the screwdriver in t...

Page 24: ...bles are permitted Signal cables must not be let within the same cable shaft as high voltage cables As soon as the Touch Panel is provided by power supply the Touch Panel starts with user area of the VIPA Startup Manager On delivery the button Advanced is shown at the starting screen Further buttons and their properties may be configured in the administrator area with the button Settings or freely...

Page 25: ...stored The backed up files may be restored by Restore Here you get information about Touch Panel like operating system images runtime version and tools With this button you may return to the user area With the button Control Panel or with Start Settings Control Panel the system settings like brightness and contrast of the display may be preset or the display may be re calibrated Here the communica...

Page 26: ...ed at Settings are activated With disabling Run on Startup the Touch Panel starts with the Windows operating system The functions preset at Settings are ignored With enabling Enable User Interface the Touch Panel starts with the Startup Manager the listed functions of Copy and Execute are executed and the program marked with Autostart is executed If Enable User Interface is disabled the Touch Pane...

Page 27: ...n the user respectively administrator area Here new buttons may be configured and assigned with corresponding programs You may choose Normal for the user area or Advanced for the administrator area With a new button may be added Designate the button and click at to assign the button to a program The button may be removed with Fixed Custom ...

Page 28: ...ssword is defined you were prompted to enter the password If there is no password defined the administrator area is opened On delivery there is no password preset If you have forgot you password by enabling the checkbox Show Password the password may be displayed Here with the startup of the panel files may be copied e g from flash disk to Windows The files to be copied are added by With the corre...

Page 29: ...d are added by With the corresponding file is removed from the list With the file may be downloaded With Autostart a program from the program list can be selected which is to be started delayed For this activate Autostart and set at Delay a delay time of 0 With Param a project can be assigned to a selected program with which it is to be started Before you select a new project a just existing link ...

Page 30: ...rface on the Touch Panel start via the button Control Panel the tool Com2 Configuration In the opened dialog window you activate the RS485 or the RS422 interface Default off To remain the settings permanently they have to be saved with KuK Tools Store To activate the changes the Touch Panel has to be restarted after configuration About Control Panel Configuration COM2 RS422 485 ...

Page 31: ...if not communicate via Movicon or zenon Via mode the interface could be set up on DP Slave Note It is possible to set up the DP slave with the tool via software but the hardware of the Touch Panel doesn t support this In this case MPI does not work either To remain the settings permanently they have to be saved with KuK Tools Store To activate the changes the Touch Panel has to be restarted after ...

Page 32: ... runtime version of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via MPI field bus and Ethernet During operation your operating device communicates with the according PLC and reacts to the application courses in the PLC according to the configured processes Via dialogs configu...

Page 33: ... platform for a multiplicity of communication and data processing devices The functions like multi tasking and multi threading are supported by this operating system Windows Embedded CE 6 0 supports some file viewer and an Internet browser ftp http Telnet and VNC server RAS server ActiveSync file transfer USB RS232 RDP Remote Desktop Protocol Internet Explorer 6 Registry Editor WordPad Mouse point...

Page 34: ... no object is selected a frame is created by the dragging that selects the touched objects Characteristics with Windows Embedded CE 6 0 In the Professional Plus version mouse functions are fully supported As soon as the touch screen is touched with the pen a mouse pointer is shown on the desktop at the pen position The windows may be moved via the head bar Here you may also find the OK button to c...

Page 35: ...fers you access to all components of your Touch Panel like e g applications system settings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for minimizing The switch between the applications is performed via this buttons 3 Network connection As soon as your Touch Panel is connected via Ethernet you can see here the Ethernet...

Page 36: ... exclusively entered via the software keyboard Keyboard Normal At pushed SHIFT key Meaning Home Position 1 End End BS Backspace up dn lt rt pgup Page pgdn Page ins Insert del Delete Tab Tabulator Shift Caps Lock The software keyboard allows you to enter key entries without connecting an external keyboard As soon as an entry is required the software keyboard is automatically shown Hide Input Panel ...

Page 37: ...register Double Tap you may use the grid pattern to preset a double click velocity and test this on the symbol below OK takes over the set value The calibration of the touch screens happens via the register Calibration by following the instructions Set Ethernet parameters The dialog field for pre setting an Ethernet address is to be found at Start Settings Network and Dial up Connections The defau...

Page 38: ...or the Touch Panel Baud Rate Enter here the transfer velocity of your MPI net The baud rate has to be identical for every MPI participant within the network According to the Baud Rate the network parameters are set Default Net Parameters It is recommended not to alter the Default Net Parameters that are set by the baud rate Status The status of the MPI interface is monitored via Status as Offline ...

Page 39: ... data transfer Before you may access the Touch Panel from the PC via ActiveSync you have to install it on the PC ActiveSync is freeware and may be downloaded from www microsoft de Download the ActiveSync from the Microsoft website and start the file MSASYNC EXE The following dialog window appears Start the installation with Next Choose an installation directory and click on Next ActiveSync is inst...

Page 40: ...e Touch Panel is recognized and the dialog window new partnership opens Choose yes for fixing a partnership and push Next In the now opening window de activate all synchronization settings and click on Next Finish establishes the partnership Now you may access the Touch Panel with ActiveSync via USB Note To keep the settings also after power on you have to store them to the registry with START Pro...

Page 41: ... via START Programs KuK Tools before switching off Per default the following server are integrated ftp server activated http server activated Telnet activated VNC not activated Phrases that are used in the description of the server A client is an application that uses the service of a server within a network For example a web browser is a client because at every call of a website it sends a reques...

Page 42: ...a ftp connection If there are still problems with the ftp access please ask your system administrator ftp access possible with version 5 5 or higher use passive ftp mode activate directory view for ftp sites For the adjustment choose in the Internet Explorer Options Internet options register extended in the area Browsing and set the following settings activate activate directory view for ftp sites...

Page 43: ... your Touch Panel with the network where your PC is a member via an Ethernet cable Switch on your Touch Panel As soon as your Touch Panel is connected via Ethernet you may monitor the IP address data via After you ve confirmed the pre settings start your ftp client and enter the following text into the address bar ftp wince vipatp IP Adresse The following window appears Here you may execute the re...

Page 44: ...the PC As web admin you have access to all functions that are required for uploading and administrating of websites on the Touch Panel Additionally you may set the access rights for user and create user groups More detailed information about creating and administrating of websites on the Touch Panel are available in the online documentation of the web servers The login as web admin requires the fo...

Page 45: ...lication is not possible The establishing of a Telnet connection is password protected and has the following approach Start a Telnet client like for example MS DOS console at your PC and enter the following into the address bar telnet IP address When the connection is established the Touch Panel asks for the user name and the password Enter the following Login wince Password vipatp entry is hidden...

Page 46: ...M JEE0 Rev 11 14 After establishment of a Telnet connection the Touch Panel provides you with commands A list of possible commands with a short description is available via the command help By beginning with help before a command you receive help to this command Commands ...

Page 47: ...pproach Click on and open the Windows directory You have to deactivate every option at View Options to show the VNC server file Start the VNC server by executing the file winvnc exe To show the server has been started the symbol appears in the task bar You may also start the VNC server at the Touch Panel via a Telnet connection by entering the command winvnc in the command console with an active T...

Page 48: ... server To test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection of a local name at the Touch Panel with a shared drive of the network PC happens with the following approach Enter the following in the command prompt net use local_name network drive user User name Enter user name password and wher...

Page 49: ...etwork printer For example you may print the content of the current directory using dir network printer The listing command for all network connections of your Touch Panel is net use You may terminate already assigned network resources via net use local_name d Example net use data d deletes the network connection to the drive archive of test server Note To save the settings also after power on you...

Page 50: ...mware and navigate via HMI to the firmware for your Touch Panel Transfer the files to your PC Copy the os file to your storage medium Unzip the zip file with directory structure to your storage medium Switch on the power supply of your Touch Panel and plug in the external storage medium After the panel start up navigate to your storage medium and execute the os file Now will be checked whether the...

Page 51: ...l Here we describe possible paths how interference can enter the controller how you ensure the electromagnetic compatibility EMC and how to approach shielding and screening issues Topic Page Chapter 3 Installation Guidelines 3 1 Basic rules for the EMC equitable assembly of installations 3 2 EMC equitable assembly 3 6 EMC equitable cabling 3 7 Special precautions providing high noise immunity 3 11...

Page 52: ... industrial environments and complies with EMC requirements to a large degree In spite of this you should implement an EMC strategy before installing any components which should include any possible source of interference Electromagnetic interference can enter your system in many different ways Fields Bus Power PE I O Signal Automation System Interference is coupled into your system in different w...

Page 53: ...ate to the temporal change of the voltage Interference through parallel signal lines Static discharge of the personnel Contactors Inductive coupling Automation System Disruptor inductive coupling line wanted signal Inductive or magnetic coupling occurs between two current active line loops The magnetic flows associated with the currents induct interference voltages The coupling is proportional to ...

Page 54: ...groups High voltage lines power supply lines signal lines data lines Always install high voltage lines and signal or data lines in separate channels or bundles Install signal and data lines as close as possible to any metallic ground surfaces e g frames metal rails sheet metal Ensure that the screening of lines is grounded properly Data lines must be screened The screen has to be laid both sided A...

Page 55: ...scent lamps Create a single reference potential and ensure that all electrical equipment is grounded wherever possible Ensure that grounding measures are implemented effectively The controllers are earthend to provide protection and for functional reasons Provide a star shaped connection between the plant cabinets cubicles and the grounding protection system In this way you can avoid ground loops ...

Page 56: ...at may only get voltage in case of an error The ground must not adopt dangerous contact voltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid ground loops local distant ground constructions cubicles construction and machine parts have to be connected with the protected earth conductor system in star topology Please regard at grounding Conn...

Page 57: ... to divide the cables in different groups and install each group itself Group A screened bus and data lines screened analog lines unshielded lines for direct voltage 60V unshielded lines for alternating voltage 25V Coaxial cables for monitors Group B unshielded lines for direct voltage 60V and 400V unshielded lines for alternating voltage 25V and 400V Group C unshielded lines for direct and altern...

Page 58: ... be installed on metallic cable trays A galvanic connection must be provided for joints between cable trays You must abide by the applicable lightning protection and grounding regulations when installing exterior cables Attention Where cables and signal lines for PLC equipment are installed outside of buildings the conditions for internal and external lightning protection must be satisfied Exterio...

Page 59: ...mm 2 Cu for equipotential bonding conductors up to 200m 25mm2 Cu for equipotential bonding conductors exceeding 200m Use copper or galvanized steel for equipotential bonding conductors These must be connected to ground neutral by means of large surface connections that are protected from corrosion The equipotential bonding conductor should be installed in such a manner that it includes the smalles...

Page 60: ...s recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to the screening neutral rail Note Potential differences can give rise to an equalization current via the screen connected between the two ground connections In this case you must install an additional equipotential bonding conductor Please observe the following points when you ...

Page 61: ...nections of DC activated inductors Connections of AC activated inductors using a diode using a Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU These outlets must be wired to the distribution system which is also used to connect the neutral conductor for the cubicle The cubicle illumination should consist of incandescent lights e g LINESTRA la...

Page 62: ...al contact washer Have the connection been protected from corrosion e g by means of grease Have doors been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabling divided into groups Power cables 230 400V and signal lines installed in separate channels or bunches Potential compensating When installing the equipment at separate locations check the installati...