Chapter 1 Basics and Assembly
Manual VIPA System SLIO
1-8
HB300E - IM - RE_053-1DN00 - Rev. 11/21
The modules were directly be mounted to the mounting rail and so
connected to the backplane bus and the power supply for the electronic
and power section.
Up to 64 modules may be mounted. Please consider here that the sum
current of the electronic power supply does not exceed the maximum value
of 3A. By means of the power module 007-1AB10 the current of the
electronic power supply may be expanded with 2A. More about this may be
found at "Wiring".
•
Mount the mounting rail! Please consider that a clearance from the
middle of the mounting rail of at least 80mm above and 60mm below,
respectively 80mm by deployment of shield bus carriers, exist.
80
m
m
8
0m
m
60
m
m
65
m
m
•
Start at the left side with the head module (e.g. bus coupler). For this
turn both locking lever upwards, put the head module to the mounting
rail and turn both locking lever downwards.
•
Before mounting the periphery modules you have to remove the bus
cover at the right side of the Head module by pulling it forward. Keep the
cover for later mounting.
1
2
Mounting
Proceeding
Mounting
mounting rail
Mounting
Head module
(e.g. bus coupler)
Summary of Contents for SLIO IM 053-1DN00
Page 1: ...VIPA System SLIO IM 053 1DN00 Manual HB300E_IM RE_053 1DN00 Rev 11 21 May 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DN00 Rev 11 21...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DN00 Rev 11 21...
Page 28: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 20 HB300E IM RE_053 1DN00 Rev 11 21...