Chapter 2 Decentral block periphery CAN-Bus CANopen
HB100E - SM-CAN - Rev. 15/02
2-39
Index
Sub-
Index
Name
Type
Attr. Map.
Default value Meaning
0x6202
0x00 8-bit
digital
output block
Unsigned8
ro
N
0x01
Number of available digital 8-bit
output blocks
0x01
1.
output
block
Unsigned8
rw
N
0x00
1. polarity digital output block
Individual negation of the output channels
1 = output inverted
0 = output not inverted
Index
Sub-
Index
Name
Type
Attr. Map.
Default value Meaning
0x6206
0x00 8-bit
digital
output block
Unsigned8
ro
N
0x01
Number of available digital 8-bit
output blocks
0x01
1.
output
block
Unsigned8
rw
N
0xFF
1. error mode digital output
block
With the help of this object you may define, if an output channel changes at
an error event to a specified value, predefined in the object 0x6207.
1 = take the value in object 0x6207
0 = fix output value at error event
Index
Sub-
Index
Name
Type
Attr. Map.
Default value Meaning
0x6207
0x00 8-bit
digital
output block
Unsigned8
ro
N
0x01
Number of available digital 8-bit
output blocks
0x01
1.
output
block
Unsigned8
rw
N
0x00
1. error value digital output block
Presupposed that the error mode is activated, at an error event the here
predefined value is taken.
1 = At error event output value to 0 as soon as object 0x6206 is activated.
0 = At error event output value to 1 as soon as object 0x6206 is activated.
8Bit change polarity
digital outputs
8Bit error mode
digital outputs
8Bit error value
digital outputs